S&P CAIB - BE Manual De Instrucciones página 24

Aerotermo centrífugo en caja insonorizada
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Connection to a second motor (running at the speed settings of the CAIB motor) or a damper.
Information on the status of the HS and LS contactors is duplicated to permit
control of a second fan or an "all-or-none" incoming air damper.
This information is given in the form of a voltage-free contact (21-24) (breaking
power 5 A max. /230 V ). This can control:
-
A single-phase motor (directly) ( In = 5 A max.)
-
By relay: the power contactor control
-
A damper servo-motor.
The N / L1 power supply can be restored from the switch isolator present in the
controller.
N
L1
22
24
21
22 24
21
(Motor circuit
breaker)
N
PV
GV
Motor
5A/230V
Single phase 230Vac
2-speed motor
Contactors Kmpv and Kmgv
Circuit breaker
Controller
24V
24V
(DEMZ box )
Controller
22
24
21
22
24
21
Three-phase 400Vac
2-speed motor
Markings on KMpv and KMgv contactors
L1
22 24
21
22
24
21
L1
commande
N
motor de registro
Paro/Marcha 230V
7 8 9 10 11 12
- +
G
G0
ANACRONO
+ -
1 2 3 4 5 6
caja de
regulación

Publicidad

Tabla de contenido
loading

Tabla de contenido