Descargar Imprimir esta página

Allen-Bradley 100-E2650 Instrucciones De Operación página 2

Publicidad

General
this interface allows the contactor to accept a very wide voltage range.
The Contactor can also be controlled by separate logic control signals from,
for instance, a PLC. Selection of control method is done with switch S1.
Control by switching voltage on A1 and A2 requires the switch in position B
while control with logic signals requires the switch in position A. Use of the
logic control signals also requires a steady supply voltage on A1 and A2
within the rated voltage range.
Control by switching voltage on A1 and A2 (switch S1 in
position B, default factory setting).
Operation of 100-E contactors can be done as with conventional contactors
by applying and removing voltage on A1 and A2.
Control with logic control signals (switch S1 in position A)
Use of the logic control signals also requires a steady voltage on terminals
A1 and A2 within the operational limits. Minimum pluse length for opening
and closing: 7ms. The function of the logic control signals will no longer be
guaranteed when the voltage on A1 and A2 is removed. The logic control
signals operates with 24V DC and consists of two control signals (ON and
OFF_N) and a common reference (COM).
ON
OFF_N
COM
+24V
Start
0V
Note: Emergency stop should disconnect A1 and A2
When used with switches the wiring can be done
according to the following diagram.
The functions are descibed with following diagram. "1" means 24V DC
between the control signal and COM, "0" means no voltage between the
control signal and COM. The function is made so that ON and OFF_N can
be connected in parallel for a common ON/OFF signal. In addition to these
signals the function limits for the supply voltage are still valid (closing at
77% and opening at 55%), which is indicated in the diagram by high and
low voltage.
PLC
PLC
PLC
Supply voltage
A1
A 2
Contactor
ON
Stop
OFF_N
COM
Position
Contactor
closed
Contactor
open
Wire dimensions for PLC interface.
X 5
O N
1
O N
2
O F
F _
3
N
C O
M
S 1
A
P L
B
C
P L
C
+24V
Start
Stop_n
0V
Note: Emergency stop should disconnect A1 and A2
When used with transistor outputs the wiring can be done
according to the following diagram.
24V DC Signals:
Status "1" : U=15...33V DC
Status "0" : U=0...5 V DC
1
ON
0
1
OFF_N
0
1
Supply voltage
on A1 and A2
0
Closed
Position
Open
Low
High
Normal range
Operational limits
77% of lower range level
55% of lower voltage range level
Wire strip length
3 x 0.2...2 mm²
3 x AWG 22 ... 14
5-6 mm
(0.2-0.24 in)
X 5
O N
1
O N
2.6 lb-in
2
O F
0.3 Nm
F _
3
N
C O
M
S 1
A
P L
B
C
P L
C
ø 3.5 mm
(0.14 in)
Supply voltage
A1
Contactor
ON
OFF_N
COM
I =10mA at 24V DC
2/6
Control
voltage
A2

Publicidad

loading

Este manual también es adecuado para:

100-es3-11100-es4-11100-es3-b01100-es3-b10