Annex - A
Technical data (English)
Name plate
A
OP-MSXM034MLW05E
114X7062
B
C
Application
MBP
Refrigerant
(1) R404A, R452A, R507,
D
R448/9A, R454C, R455A
M.W.P. HP
(1) 28 bar
E
LP (1) 7 bar
Voltage
380-400V~3N~50Hz
F
LRA
30,5 A
Serial No.
123456CG4818
G
Barcode Serial No:
EAN No.
XXXXXXXXXXXXX
* For exact values please refer name plate in unit
A: Model
B: Code number
C: Application, Protection
D: Refrigerant
E: Housing Service Pressure (Maximum working pressure)
F: Supply voltage, Locked Rotor Ampere, Maximum Continuous Current
G: Serial Number and bar code
Designation system for the Optyma™ Slim Pack range
OP - MSXM
034 ML W05 G
1 2 3 4
5
1 Application
M = MBP
L = LBP
2 Package
Condensing unit family: S = Slim Pack
3 Refrigerant
T = R404A/R507, R455A, R454C, R448A/R449A, R452A
S = R134a, R513A, R1234yf
V =R454C, R455A, R452A, R404A/R507
4 Condenser
M = Microchannel heat condenser
5 Swept volume
Displacement in cm
Example 034 = 34 cm
3:
6 Compressor platform
(Such as DP/DX/DS = Fixed speed Reciprocating compressor)
7 Version
W05: Optyma™ Slim Pack standard version (see Version table)
8 Voltage code
G = 230V/1-phase compressor & fan
E = 400V/3-phase compressor & 230V/1-phase fan
30 | AN37261865152501-010101 - 118A2176A
MADE IN INDIA
IP54
(2) R134a,R1234yf,
R513A
(2) 23 bar
(2) 5 bar
MCC
7,5 A
PS = 32 bar
Danfoss A/S, 6430 Nordborg, Denmark
6
7
8
3
N
Picture 1 : Minimum mounting distances
L
M
[mm]
[mm]
250
50
Version control
Optyma™ Slim Pack
Condensing unit :IP level
Refrigerant
Compressor technology
Control box (pre-wired E-panel)
Microchannel condenser
Fan speed controller
Main switch (circuit breaker)
Filter drier (flare connections)
Sight glass
Crankcase heater
HP/LP adjustable pressostat
Access door(s)
Acoustic insulation
Discharge gas thermostat
HP/LP Alarm
Electrical Box design
Adjustable time delay (Compressor)
* Compatible with A2L refrigerant
L
O
L
M
N
[mm]
[mm]
550
W05*
IP54
Group I / Group II
Reciprocating
yes
yes
-
-
yes
yes
yes
Auto/Manual reset mode
yes for E-Box
-
yes * (Provision)
yes* (Provision)
IP54
yes