MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).
4.5.3
To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover.
2 Connect the interconnection cable and power supply as follows:
c
d
a
e
a
Interconnection cable
b
Power supply cable
c
Earth leakage circuit breaker
d
Fuse
e
User interface
V1
c
c
d
e
f
a
Switch box
b
Stop valve attachment plate
c
Earth
d
Cable tie
e
Interconnection cable
f
Power supply cable
AZQS100~140B8V1B + AZQS100~140B7Y1B
Split system air conditioners
4P385528-1C – 2016.10
100
32 A
V1
Y1
1~50 Hz
3N~50 Hz
220-240 V
380-415 V
L1 L2 L3
b
b
L1 L2 L3
N
a
b
Y1
c
c
d
e
f
AZQS_V1
125
140
40 A
Must comply with applicable legislation
3 Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate.
4 Route the wiring through the frame and connect it to it.
Routing through
the frame
Connecting to the
frame
5 Reattach the service cover.
6 Connect an earth leakage circuit breaker and fuse to the power
supply line.
4.6
Finishing the outdoor unit
installation
4.6.1

To finish the outdoor unit installation

1 Insulate and fix the refrigerant piping and interconnection cable
as follows:
c
a
b
f
a
Gas pipe
b
Gas pipe insulation
4 Installation
AZQS_Y1
100
125
16 A
20 A
Choose one of the 3 possibilities:
2
1
b
b
a
a
a Power supply cable
b Interconnection cable
When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.
When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.
A B
a b c
d
e
A Inside of the outdoor unit
B Outside of the outdoor unit
a Wire
b Bush
c Nut
d Frame
e Hose
d
e
Installation manual
140
25 A
3
b
a
9

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Azqs125b8v1bAzqs140b8v1bAzqs100b7y1bAzqs125b7y1bAzqs140b7y1b

Tabla de contenido