Operation
Dry Contact Test (#31) - Selecting the DRY CONTACT TEST option will simultaneously
test all output dry contacts for 1 minute. To initiate a DRY CONTACT TEST, navigate to
the DRY TEST screen and select ON or OFF for the desired testing configuration.
Dry Contact Test
0) Off
1) On
2) Cancel
>
External Fan Test (#32) - Selecting the EXTERNAL FAN TEST option will test the
external fan for a period of 1 minute. To initiate an EXTERNAL FAN TEST, navigate to
the EXT FAN TEST screen and select ON or OFF for the desired testing configuration.
External Fan Test
0) Off
1) On
2) Cancel
>
UPS Output (#33) - Selecting the UPS OUTPUT option enables the setting of UPS
output power to be OFF or ON in Inverter, Boost, Buck and Normal Modes. To turn
UPS OUTPUT OFF or ON in these operating modes, navigate to the UPS OUTPUT
screen and select the ON or OFF setting.
Select ON to enable UPS output in Inverter, Boost, Buck and Normal modes.
Select OFF to disable UPS output in Inverter, Boost, Buck and Normal modes.
UPS Output
0) Off
1) On
>
Reset Event (#34) - Selecting the RESET EVENT/TM option resets all EVENTS and
TIME DURATIONS stored in the UPS. To reset all events and times, navigate to the
RESET EVENT/TM screen and select YES or NO from the sub-menu options.
Reset Event/TM
0) No
1) Yes
>
33