EXHAUST FLUE INSTALLATION
CONCENTRIC FLUE PIPE
Fit the concentric elbow pipe positioning it on the desired direction and insert on it the sealing gasket. Then fit
the appropriate diaphragm (see table below).
Fit the air intake and the exhaust pipes, observing the distances indicated on the installation scheme. The
exhaust pipe should slope slightly outward.
100
Max. 3000
DOUBLE PIPE
** Air intake Ø 80
ATTENTION: Use only air intake/ flue gas evacuation kits produced by Lamborghini Caloreclima.
100
220
440
Max. length
0,5 ÷ 1m
Diaphragm
Ø 80 mm
Maximum length of CONCENTRIC PIPE 3 m
Maximum length of DOUBLE PIPE
(Intake + Exhaust) 20 m
Installing an elbow to connect the boiler to the chimney will cause a
drop in pressure.
The values set out in the table below indicate the necessary
modifications to the length of the linear pipes.
TYPE OF INSTALLATION
DOUBLE PIPE INTAKE/EXHAUST
Max. 3000
160
330
CONCENTRIC PIPE
over 1 m
No diaphragm
(hole standard)
CONCENTRIC PIPE
EXHAUST PIPE
Air diaphragm
DOUBLE PIPE
No diaphragm
(hole standard)
ELBOW FITTED
ELBOW FITTED
AT 90°
1 m
0,6 m
49
AT 45°
0,5 m
0,3 m