Each notification appliance output provides connected notification appliances with a
maximum current of 500 mA at 24 VDC. The permissible voltage range of the output is 21–
29 VDC.
1.7.5
Relay outputs
Notice!
The fault relay is activated in a normal state. It is opened in the event of a fault.
1.8
Commissioning
1.8.1
Setting the language
To set the language, proceed as follows:
ACK
1.8.2
Setting the time and date
ACK
Repeat this procedure to set the correct values for the month, year and time.
After initializing the fire panel you are in the basic settings of the panel.
Bosch Sicherheitssysteme GmbH
NO C NC
ALARM
Use the arrow keys to set the desired language.
i
Confirm your selection in the menu with the ACK key.
Use the arrow keys to set the current day.
i
Confirm your selection in the menu with the ACK key.
NO C NC
FAULT