Installation
Mounting
1
2
800 A: 10 x
1200 A: 6 x
Mounting the safety switch on the wall
or other supporting structure
Mount the safety switch using 5/16" screws (for 800 A: 10 pcs
and for 1200 A: 6 pcs). Note: Use the keyslot mounting hole
(in 800 A switches) to hang the enclosure while securing the
other mounting screws. Verify that the load-carrying capacity
of mounting wall or supporting structure is sufficient in relation
to the weight, size and way of fixing of safety switch and in
accordance with local requirements.
Anchorage:
– wall-mounted
– mount cabinet on flat surface to avoid distortion
– use shims if necessary
800 A
1200 A
CAUTION
HAZARD OF INJURY OR EQUIPMENT DAMAGE
Do not in any circumstances bend or twist the locking hook fixed on
the door. Wrong position of the door hook causes the malfunction of
the locking mechanism that may result in personal injury or equipment
damage.
Failure to follow these instructions can result in injury or equipment damage.
Instruction Bulletin EOHU367/8J/R/S/SS, 1SCC340040M1401 / A | Installation 1/11