TOF/Start
Important:
The scale is not printed on the sensor. However the
potentiometer can be adjusted in five fixed steps of 0.2
m; starting at 0.6 m (at the 7 o'clock position) up to 1.4
m (at the 5 o'clock position); see Figure 3 below.
Take a small screw driver and turn the potentiometer to
the required position.
x = min. 600 ... max. 1400
Figure 3:
Detection area using potentiometer
Parameter
Value
Width (x-axis)
Min.: 600 mm
Max.: 1,400 mm
2,000 mm
Length (y-axis)
Aperture angle
70°
Table 1:
Parameter - detection area
6.
Installation
Important:
The TOF/Start must be mounted under the handrail at
a minimum 10° mounting angle to the ground facing
upwards.
10°
Figure 4:
Mounting angle of TOF/Start
© CEDES | V 1.1
7.
Generally the TOF/Start has one output that is triggered if
the detection field is interrupted. For this purpose, a push-
pull output is used. With the logic selector (gray wire, Figure
6), the logic of the output signal can be configured for
"HIGH" on object or "LOW" on object operation (Figure 5),
according to the controller requirements.
The logic selection is performed during start-up.
Logic selector connected to U
Output
Logic selector connected to GND (0 V)
Output
1.0 m
1.2 m
0.8 m
0.6 m
1.4 m
Figure 5:
x-axis
TOF/Start
(all dimensions in mm)
n.c. = not connected and isolated
Figure 6:
8.
1. Switch on mains and power up.
2. Check if LED lights up.
3. Check the distance setting and the reaction of the
sensor, including the status LED, by placing an object
into the detection area at different heights and widths.
Input / Output description and
electrical connection
SP
U
SP
0 V
U
SP
0 V
Output (PNP/NPN) logic
U
SP
Output
n.c.
GND (0 V)
n.c.
Selectable output logic
Connection diagram
Start-up
English
brown
black
green
blue
white
gray
5