Introduction And Specifications - SJE VFDC-3000 Manual Del Usario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Congratulations and thank you for your purchase of the VFDC-3000 controller. This manual explains the
features and operations of the controller which was designed to operate up to 3 pumps in a constant pressure
application. The controller automatically adjusts pump speed and the on and off pump sequence in response
to changes in the system pressure. When used to control the system pressure, a 4-20mA pressure transmitter
is connected to the input. The controller features a rotary selector knob in addition to left shift and escape
push buttons for intuitive menu navigation and quick setting adjustments.
GENERAL
• One, two or three pump constant pressure
controller
• Operates using 4-20mA pressure transmitter
• Rotary selector for menu navigation
• 2.7" blue OLED 64 x 256 pixel display
DIMENSIONS
• 7.2 x 5.3 x 2.0 inches (18.3 x 13.5 x 5.1 cm)
PUMP CONTROL AND PROTECTION
• Automatic pump sequencing
• Multiple sequencing configurations
• Automatic pump sequencing on VFD fault
• Pump run indication
• Variable speed
SYSTEM
• Alarm counts
• Number of starts for each pump
• Run time for each pump
SJE
®
INTRODUCTION & SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
• 24 VDC Class 2 (19-28 VDC, 325mA max)
DEDICATED I/Os
• 4 digital inputs (low suction, high pressure,
low water, setpoint pressure 2)
• 6 relay outputs (configurable, 30 VAC/DC,
3A Max.)
• 1 analog input (4-20mA, 14 bit resolution,
non isolated)
MODBUS COMMUNICATION:
• Dedicated communication port for Mitsubishi
VFD control
ENVIRONMENT
• Operational temperature 32 to 122º F (0 to
50º C)
• Storage temperature -4 to 140º F (-20 to
60º C)
• Relative Humidity (RH) 5% to 95% (non-
condensing)
• Indoor rated - for indoor use or mounted
inside of an outdoor rated enclosure.
2
VFDC-3000 Controller User Manual

Publicidad

Capítulos

Tabla de contenido
loading

Productos relacionados para SJE VFDC-3000

Tabla de contenido