suspended.
• Low Pressure Alarm Reset Delay Time
The Low Pressure Alarm Reset Delay Time setting should be set to the time after a Low Pressure Alarm
flag is set until the system automatically resets. Upon automatic reset, the Low Pressure Alarm flag is
cleared and normal operation of the controller resumes. If a manual reset of the Low Pressure Alarm is
desired, set the Low Pressure Alarm Reset Delay Time to "0.0".
High Pressure Alarm
The High Pressure Alarm is used to notify the user and stop the pumps if the system pressure exceeds the
High Pressure Alarm setting. The High Pressure Alarm automatically resets after the system pressure drops
below the High Pressure Alarm setting.
Low Water Delay Time
The Low Water Delay Time setting should be set to the amount of time after a Low Water input is active,
before the Low Water flag is set and pump operations are suspended.
SJE
®
7
VFDC-3000 Controller User Manual