Electrical Installation
Electrical Installation
Solar modules from LG Electronics dealt
with here meet the requirements of Ap
plication Class A: Dangerous voltage (IEC
61730: more than 50 V DC; EN 61730:
more than 120 V DC); systems with dan
gerous power where normally unlimited
accessibility is expected.
For more information on solar modules
from LG Electronics, please refer to the da
tasheets of the solar modules. These can
be found at www.lgsolar.com.
In particular ambient conditions, a solar
module can deliver a higher current
and / or voltage than indicated in the
standardised test conditions. For deter
mining the rated values of components
such as cabling, fuses and inverters con
nected to the solar module's outlet, the
values for I
and U
sc
oc
by a factor of 1.25 when the photovoltaic
systems are designed.
are to be multiplied
General Wiring
Solar modules from LG Electronics can
be connected in series or parallel to get
the desired electrical output.
Use only solar modules of the same type
in a combined connection.
EN
29