Commissioning RF Set
1
Switch on REV200...RF
•
Remove the battery transit tab (also refer to Fig. 7): As soon
as the battery transit tab is removed, the unit starts to operate.
2
Mount REV-R.03... temporarly
•
If possible, mount receiver temporarly in a first run (e.g. double
coated tape). Doing that, location of best RF reception can be
identified later on.
See clause "5 Find location of best reception"
•
Completely wire and mount REV-R.03... temporarly. Proceed
according Fig. 12 to 14 (please also close front cover)
3
Link REV-R.03... with REV200...RF
a)
Switch on power at REV-R.03...: LED_1 (Fig. 12) lights always
in red or flashes in red
b)
Press the "RESET" button on REV-R.03... for about
4 seconds: The orange LED_2 (Fig. 12) will flash very fast
and briefly (stored address of REV200...RF will be erased)
c)
Press the "SET" button (set / learn) for about 3 sec. until the
orange LED starts flashing slowly and continuously: Receiver
is now in learning mode
d)
The receiver stays max. 25 minutes in learning mode. If no
learning telegram from REV200...RF is received during that
period of time, repeat steps b) and c) again
e)
Press the "Learn" button on REV200...RF for about
4 seconds. Learning telegram is transmitted
f)
If REV-R.03... receives learning telegram, the orange LED_2
flashes fast and briefly
g)
If the orange LED_2 is steady on, the relay is energized
(= controlled device ON)
h)
If the orange LED_2 is dark, the relay is deenergized
(= controlled device OFF)
i)
Depending on the operating state, REV200...RF repeats the
ON or OFF control telegram every 3 minutes. With this the
relay will be switched ON or OFF according to control telegram
latest after 3 minutes
j)
If REV-R.03... does not receive any correct control telegram
within 60 minutes, controlled device is being switched off and
LED_1 flashes in red
k)
In the event of a power failure at the REV-R.03..., the relay will
be deenergized.
4
Site REV200...RF
•
Site REV200...RF at preferred location for mounting at wall or
setting up with stand. Remove the unit from its base by
proceeding according to Fig. 1 to 3:
- for wall mount, refer to Figs. 4 to 10
- for set up with stand, click the stand to the backside of
base.
•
Also refer to "Mounting and siting notes REV200...RF and
REV-R.03..."
5
Find location of best RF reception
a)
Switch off power at REV-R.03...
b)
Switch on REV200...RF, site at prefered location and press
override button "Test" for about 4 seconds: REV200...RF
transmits test telegrams every 2 seconds. Transmission of test
telegrams stopps automatically after 10 minutes or after
pressing "Test" button.
c)
Switch on power at REV-R.03...
d)
Observe both LEDs on REV-R.03... from a distance of
2...3 meters
e)
Orange LED_2 must flash briefly every 2 seconds.
Does LED_2 not flash every 2 seconds, distance between
REV200...RF and REV-R.03... is too far. Mount REV-R.03...
closer to REV200...RF
f)
LED_1 shows received signal strength of last telegram:
LED_1 flashes red:
Signal is too weak to get a durable
durable link. Mount REV-R.03...
closer to REV200...RF
LED_1 flashes green: We distinguish between three
signal strenghts:
Building Technologies / HVAC Products
g)
Move REV-R.03... within an area of approximately 1 square
meter to find location of best RF reception. Always observe
LEDs from a distance of 2...3 meters.
To get a durable link, we recommend to site REV-R.03... at
a location where signal strength is at least "Good".
6
Explanation to LED_1 and LED_2
LED_1 lights always in red:
Red on
Red off
LED_1 flashes in red:
Red on
Red off
LED_1 flashes 3 times in green:
Green on
Green off
Starting
LED_1 flashes 2 times in green:
Green on
Green off
Starting
LED_1 flashes 1 time in green:
Green on
Green off
Starting
LED_2 is always dark:
Orange on
Orange off
LED_2 lights always:
Orange on
Orange off
LED_2 flashes always:
Orange on
Orange off
LED_2 flashes briefly: Reception of control telegram
G2214xx
Very good (flashes 3x),
Good (flashes 2x) and
satisfactory (flashes 1x).
As soon as LED_1 flashes in green,
link between REV200...RFand
REV-R.03... is basically ok.
No REV200...RF linked
Signal strength too weak
Signal strength: Very good
1 2 3
1 2 3
Starting
Signal strength: Good
1 2
1 2
Starting
Signal strength: Satisfactory
1
1
Starting
Starting
Controlled device OFF
Controlled device ON
Learning mode active
09.02.2007
Starting
1