Parameters; Parameter Descriptions - BriskHeat SDC Manual De Instrucciones

Controlador de temperatura digital de mesa
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

PARAMETERS

Description
Set Point
SP
Differential or Hysteresis
r0
Low Value Set Point
r1
Higher Value Set Point
r2
Heating or Cooling Control
d0
Min. Stop Time for Load
c0
Load Status During Probe Error
c2
Probe Adjustment
P1
Probe Type
P5
Probe Response
P6
Parameter Access Code
H5
Alarm 1 Hysteresis
A0
Alarm 1 Threshold
A1
Alarm 1 Exclusion Time
A2
Alarm 1 Configuration
A3
Alarm 2 Hysteresis
A4
Alarm 2 Threshold
A5
Alarm 2 Exclusion Time
A6
Alarm Configuration
A7
®
© BriskHeat
Corporation. All rights reserved.
SDC Benchtop Digital Temperature Controller
Units
Range
Degrees
r1 to r2
Degrees
1 to 99º
Degrees
0 to 999º
Degrees
0 to 999º
Option
Ht/Co
Minutes
0 to 59
0/1
Off/On
Degrees
-30° to +30º
Option
J, K, S
Numeric
0 to 3
Numeric
0 to 255(factor set 0)
Degrees
1 to 999º
Degrees
0 to 999º
Seconds
0 to 999
Option
Off, Lo, Hi
Degrees
1 to 999º
Degrees
0 to 999º
Seconds
0 to 999
Option
Off, Lo, Hi
5
SETTING THE SP

Set point (SP) is the only parameter the user can access without code protection.

Press SET and the SP text will appear on the display.

Press SET again and the real value is shown on the display.

The value can then be modified with the UP and DOWN arrows.

Press SET to enter any new values.

Press SET and DOWN at the same time to quit programming or wait one minute and the
display will automatically exit programming mode.

PARAMETER DESCRIPTIONS

SP = Set Point-Desired Regulation Temperature.
r0 = Differential or Hysteresis.
r1 = Lower Set Point Limit.
r2 = Higher Set Point Limit.
d0 = Heating or Cooling Control-regulation cycles only performed, neither defrosting nor
continuous cycles exist.
Heating: To choose heating control: Set d0=Ht (The output is active when TS1
(temperature of probe) is less than or equal to set point.) TS1<=SP. It then disconnects
when TS1>=SP-r0.
Cooling: To choose cooling control: Set d0=Co (The output is activated when
TS1>=SP+r0.) The display will switch off when TS1<=SP.
c0 = Minimum Time Between Start to Stop.
c2 = Load Status during Probe Error. In the event of an open or short-circuited probe, the unit
will connect or disconnect the load as defined by this parameter.
P1 = Probe Calibration. Offset degrees to adjust probe. If the probe is not placed in the exact
point that is to be measured, use a standard thermometer and adjust the difference with
parameter.
P5 = Probe Type. Select between J, K, or S type thermocouple.
P6 = Probe Response Rate (0 = 8 sec, 1 = 4 sec, 2 = 2 sec, 3 = 1 sec.).
H5 = Access to Probe Parameters.
A0 = Alarm 1 Hysteresis. The differential associated with A1 parameter.
A1 = Alarm 1 Threshold. Number of degrees to the working set point that initiates an alarm
condition.
A2 = Alarm 1 Exclusion Time. The amount of time the alarm is disabled from instrument
activation.
®
© BriskHeat
Corporation. All rights reserved.
SDC Benchtop Digital Temperature Controller
6

Publicidad

Tabla de contenido
loading

Tabla de contenido