Siemens SIVACON S8 Instructivo De Instalación página 12

Tablero de baja tensión con diseño verificado - celdas de salida de cable con interrup. seccion. en línea
Ocultar thumbs Ver también para SIVACON S8:
Tabla de contenido

Publicidad

Enclosure: Rated currents and configuration notes for SASIL / SASIL+ -devices
Rated currents
Permissible design current for fuse link with nominal current In:
Nominal current fuse link
In >250 A ... 630 A
In >160 A ...250 A
In >32 A ...160 A
In ....32 A
Short-time load (up to 30 min), In
Rated currents of the device sizes= F x I
For total current of all branches at the section
Size 00
50 mm high
I
= 160 A
Rated current
N
Fuse
= 122 A
Rated currents of smaller fuse links of one size = F x I
Size 00
Continuous
load current
e.g.
Fuse
I
= 125 A
x 0,76
N
=95 A
I
= 80 A
x 0,76
N
= 61 A
a1
Derating Faktor F
630 A
of the highest fuse link
N
1885 A
Size 1
75 mm high
Fuse
Rated current
I
= 250 A
= 203 A
N
of the fuse link
N
Size 1
Continuous
load current
e.g.
Fuse
I
= 224 A
x 0,81
N
= 181 A
I
= 125 A
x 0,81
N
= 101 A
0,81 x In
0,81 x In
0,76 x In
In
In
Size 2
150 mm high
Fuse
Rated current
I
= 400 A
= 324 A
N
Size 2
Continuous
load current
e.g.
Fuse
I
= 355 A
x 0,81
N
= 288 A
I
= 315 A
x 0,81
N
= 255 A
Size 3
150 mm high
Fuse
Rated current
I
= 630 A
= 510 A
N
Size 3
Continuous
load current
e.g.
Fuse
I
= 500 A
x 0,81
N
= 405 A
I
= 400 A
x 0,81
N
= 324 A
8PQ9800-7AA83

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

8pq9800-7aa83

Tabla de contenido