Technical Specifications; Warnings And Limitations - INIM Electronics EM312SR Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Technical specifications

Power supply
Current draw in standby status
Current draw in alarm status
Input balancing resistance
(terminals 5 and 6)
Alarm input resistance
(terminals 5 and 6)
Supervised output
EOL resistance
(terminals 9 and 10)
Relay contact rating
Operating temperature
Humidity (without condensation)
Height
Width (with anchor locations)
Width (without anchor locations)
Depth (with terminal boards)
Depth (without terminal boards)
Weight
The module must be connected to the control panel via a 2 pole twisted-shielded
cable. This cable carries both the power supply and the two-way digital
communications data. Refer to the Installation section for the wiring diagram.
The module has a short-circuit isolator which, in the event of short-circuit between
the two poles of the control panel loop cable, is capable of interrupting the negative
pole and thus isolating the section involved in the short-circuit. For the isolator
specification, please refer to the "ILP Specification" document.
The module should be housed inside an electrical mounting box, as per the diagram,
with the following characteristics:
• Minimal internal dimensions: 100 x 60 x 40 mm
• Protection grade IP44 or higher
• Compliant with the established standards and codes relating to the Installation of
electrical systems
The two removable serial number stickers should be taken off the
module; one should be attached to the box where the device is to
be housed, the other to the installation layout.
Once all the loop devices have been properly connected, refer to the control panel
installation and programming manual for instructions regarding the configuration
and addressing procedures.
Testing and maintenance
The functionality of the module should be tested immediately after installation and
periodically during maintenance inspections, in accordance with the established
standard regulations and codes in force.
Using the EITK-DRV driver
The EITK-DRV driver allows you to change the operating parameters of the devices
connected to the loop and also to obtain accurate diagnostic data. It can operate
through the USB port of a computer furnished with the relative software
programme, or can function autonomously by way of the battery housed inside.
For further information and details regarding use of the EITK-DRV driver, refer to
the respective handbook.

Warnings and limitations

The EM312SR module must be used exclusively with control panels that operate on
INIM OpenLoop protocol. This product is not suitable for outdoor installation.
However, if outdoor installation is necessary, ensure that the device is housed inside
a suitable enclosure with the required protection grade.
CE marking and certifications
DoP, EC DoC and certificates related to these products can be downloaded from the
following link:
www.inim.biz/certifications
INIM Electronics reserves the right to change the
technical specifications of this product without
prior notice.
4
EM312SR
19-30V
Max 80PA @
24V
20mA
@27.6V
22KOhm
2.2KOhm
22KOhm
MAX 1A /
30V
-5°C/+40°C
95% RH
53mm
100mm
78mm
29mm
19mm
66g
Installation
NO
ATTENTION!
INIM Electronics s.r.l.
Via Fosso Antico snc - Fraz. Centobuchi
63076 Monteprandone (AP) - Italy
Intelligent analogue addressable mini input/output module with
short circuit isolator for fire detection and fire alarm systems
Essential characteristics
Response delay (response time)
Performance under fire conditions
Operational reliability
Durability of
operational
reliability:
INIM Electronics s.r.l.
via Fosso Antico, Centobuchi
63076, Monteprandone, (AP) Italy
Tel. +39 0735 70 50 07
Fax + 39 0735 70 49 12
www.inim.biz info@inim.biz
EM312SR
NC
C
100 nF
22k Ohm
2k2 Ohm
0832
10
0832-CPR-F1245
EN 54-17:2005
EN 54-18:2005
EM312SR
installed in buildings
Performance
PASS
PASS
PASS
Temperature resistance
PASS
Vibration resistance
PASS
Humidity resistance
PASS
Corrosion resistance
PASS
Electrical stability
PASS
50 V
22k
Ohm

Publicidad

Tabla de contenido
loading

Tabla de contenido