TOFniva
Important:
The scale is not printed on the sensor. The
potentiometer can be adjusted linear from of 0.4 m to
2.0 m; see Figure 3 below.
Take a small screw driver and turn the potentiometer to
the required position.
1.2 m
1.6 m
0.8 m
0.4 m
2 m
y-axis
x = min. 400 ... max. 2000
Figure 3:
A type: Detection field using potentiometer
1.2 m
1.6 m
0.8 m
0.4 m
2 m
y-axis
x = min. 400 ... max. 2000
Figure 4:
C type: Detection field using potentiometer
Parameter
Value
Operating range
Min.: 0 ... 400 mm
x-axis
Max.: 0 ... 2,000 mm
Operating range
Min.: 0 ... 400 mm
y-axis
Max.: 0 ... 2,000 mm
Aperture angle
90°
Table 1:
Parameter - detection field
© CEDES | V 1.2
IMPORTANT
The cable exit of the sensor
is always at the bottom
1.2 m
1.6 m
0.8 m
0.4 m
2 m
x-axis
90°
1.2 m
1.6 m
0.8 m
0.4 m
2 m
x-axis
6.
Installation
1. Switch off main power to the control unit and mark
clearly that this system is out of service before
performing any work on the system.
2. Define the ideal place to mount the sensor
Important: The TOFniva must be mounted with a 6° angle
or with a minimum distance of 200 mm parallel to Surface
B.
3. Cut a hole at the defined position into Surface A. For
the use of the flush mounting use the delivered drilling
pattern or use a surface mounting kit. More details
about available surface mounting kit are written in the
accessories sheet of the TOFniva.
4.8
Cut-out for
flush mounting
Important: The angle type has to be mounted at a
45° angle to the detection area. The centre type can be
mounted flat (0°).
45°
4. Place the sensor and connect it according connecting
diagram in Chapter 7.
5. Switch on mains and power-up the control unit.
6. Adjust the detection field.
7. Test if the system is working correctly.
6°
Surface B
200 mm
Surface B
85
70.5
57
4.8
English
5