SBP - Sensor Board Pulse
7.4
Connecting-up
NOTES
Connection X400
60
61
62
63
64
65
66
67
7-4
The optional board has two terminal strips for the signal cables.
Connect the signal cables at the corresponding connection; terminal
X401/75 is provided for the shield.
♦ The signal inputs of tracks A, B and zero of connector X401 are
provided internally with bus terminating resistors. These are
powered up in the factory setting (switches S1-1 to S1-3 closed).
♦ The switches of the bus terminating resistors are located on the
optional board behind connector X400. Of the four switches, the
upper three in the correct installation position are responsible for the
bus terminating resistors (in the sequence A, B, zero, counting from
the top).
♦ The bus terminating resistors should normally be powered up. If
several boards are controlled with pulses from one source, all the
bus terminating resistors have to be powered down except for the
last one in the row.
♦ The power supply for the encoders can be switched OFF with switch
S1-4. The encoders must then be connected to an external supply.
As set at the factory, the encoder supply is active (S1-4 open).
♦ In the case of MASTERDRIVES MC, the power supply to the
encoders (5 V or 15 V) is adjusted by means of parameter P150 and
in the case of MASTERDRIVES VC it is adjusted by means of
parameter P139 (see Compendium, Function diagrams, Pulse
encoder evaluation).
Terminal
Designation
60
+ V
SS
61
- V
SS
62
- Temp
63
+ Temp
64
Ground rough/fine
65
Rough pulse 1
66
Rough pulse 2
67
Fine pulse 2
Connectable cross-section: 1.5 mm² (AWG 16)
Terminal 60 is at the top when installed.
Table 7-2
Connection X400
Significance
Power supply for pulse
encoder
Ground for power supply
Minus (-) connection
KTY84/PTC100
Plus (+) connection
KTY84/PTC100
Ground
Digital input
rough pulse 1
Digital input
rough pulse 2
Digital input
fine pulse 2
6SE7087-6NX84-0FF5
Option boards
SIMOVERT MASTERDRIVES
06.2005
Range
5 / 15 V
I
= 250 mA
max
3 mA
accuracy ±1 %
Siemens AG