WARNING
THIS UNIT CONTAINS A LITHIUM BATTERY AND MUST NOT BE DISPOSED OF
IN A FIRE OR EXPOSED TO TEMPERATURES BELOW -20 C OR ABOVE +70 C.
WARNING
Installation and maintenance must be carried out by suitably qualified
personnel only. Hazardous voltages may be present on the connection
terminals.
Installation
This product is intended to be installed in accordance with the operating and installation
requirements of Overvoltage Category II and Pollution Degree 2 (as defined by IEC 664).
It must be fitted in a suitable enclosure which is accessible to qualified personnel only.
The relay output circuits must be fitted with fuses suitable for the voltage and current
being switched.
Maximum fuse ratings:
250VAC
@ 8A cosØ= 1
250VAC
@ 5A cosØ= 0.4
30VDC
@ 8A cosØ= 1
All conductors carrying hazardous voltage should have external switching or disconnect
mechanisms fitted which provide at least 3mm of contact separation in all poles.
Failure to install or operate the unit in accordance with the above requirements
may result in the electrical safety of the unit being impaired.
Maintenance
Ensure that all power sources to the unit are isolated prior to maintenance,
inspection or cleaning.
There are no user serviceable parts inside this unit. Under no circumstances should the
case be opened.
All external wiring connections should be inspected at regular intervals. Any damaged
wiring should be replaced and any loose connections should be retightened.
Cleaning should be carried out using a dry cloth to wipe the casing of the unit.
ACHTUNG
DIESES GERÄT ENTHÄLT EINE LITHIUMBATTERIE UND DARF DAHER BEI
DER ENTSORGUNG NICHT VERBRANNT ODER TEMPERATUREN UNTER
-20°C ODER ÜBER +70°C AUSGESETZT WERDEN.
ACHTUNG
INSTALLATION UND WARTUNG DÜRFEN NUR VON ENTSPRECHEND GESCHULTEN
MITARBEITERN VORGENOMMEN WERDEN. AN DEN ANSCHLUSSKLEMMEN
KÖNNEN LEBENSGEFÄHRLICHE HOCHSPANNUNGEN ANLIEGEN.
Installation
Dieses Produkt ist gemäss den Betriebs- und Installationsanforderungen von
Schutzklasse II und Funkstörklasse 2 (entsprechend der Definition durch IEC 664) zu
installieren.
32
fuse rating 8A
fuse rating 5A
fuse rating 8A