Descargar Imprimir esta página

Diehl Sharky FS 473 Instrucciones De Montaje página 9

Sensor de flujo por ultrasonido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 13
English
English
6.
Temperature loads
Operating / ambient conditions
ƒ
Standard: 5 ... 55 °C; IP 54; 93 % rel. humid-
ity
ƒ
Sealed: 5 ... 55 °C; IP 68; 93 % rel. humidity
Media temperatures
Configuration
Heat - battery supplied
Heat - externally supplied
Cold - battery supplied
Cold - externally supplied
1) Only in riser / downpipe or in horizontal, tilted mount-
ing position
Note that in heat applications, the water
temperature must be greater than the
ambient temperature.
Once commissioned, avoid frost at the meter.
Use unsealed flow sensors:
ƒ
at water temperatures permanently above
ambient temperatures
Use sealed flow sensors:
ƒ
For cold applications or T
ƒ
If permanent condensation is expected
7.
Disposal
The meter (standard version) contains a
lithium battery, which is not rechargea-
ble. Do not use force to open the battery.
It must never come into contact with water,
short-circuited or exposed to temperatures over
75 °C.
Empty batteries and no longer required electronic
devices or components are hazardous waste.
This device must not be disposed together with
the domestic waste.
Return it to the manufacturer for recycling.
Temperature range
5 ... 90 °C / 5 ... 105 °C
1)
q
0.6 ... 2.5 m³/h:
p
5 ... 130 °C
q
3.5 ... 60 m³/h:
p
5 ... 150 °C
5 ... 90 °C / 5 ... 105 °C
1)
5 ... 120 °C
< T
water
ambient
8.
Declaration of conformity for MID
meters
See from page 51 onwards.
Further information as well as the actual declara-
tion of conformity are available at:
http://www.diehl.com/en/diehl-metering/
products-solutions/product-download/
Please select the partner "Diehl Metering GmbH"
and the product area "Thermal Energy Metering".
-9-

Publicidad

loading

Productos relacionados para Diehl Sharky FS 473