Program group P1
Program group P1 is used for the thermostat user settings. To
change the selected parameter, hold key
seconds. Parameter starts to flash. Press key
set the parameter value. To store the setted value, again hold
key
for approximately 5 seconds. Group P1 contains the
following parameters; (default setting):
- [P1.1] night temperature (6 °C ÷ 26 °C); (17 °C )
- [P1.2] temperature reduction in ECO mode(0 °C ÷ -9 °C); (-3 °C)
- [P1.3] frost protection temperature (0 °C ÷ 20 °C); (6 °C)
- [P1.4] holiday mode temperature (5 °C ÷ 25 °C); (12 °C)
- [P1.5] ED constant (10 min ÷ 50 min); (20 min)
- [P1.6] display of controlled device (- - - none, 1 - boiler,
2 - pump, 3 - mixing valve); (1)
- [P1.7] temperature sensor calibration (-2 °C ÷ 2 °C); (0 °C)
Service group S1
Service group S1 is used for the thermostat service settings. To
change the selected parameter, hold key
seconds. Parameter starts to flash. Press key
to set the parameter value. To store the setted value, again hold
key
for approximately 5 seconds. Group S1 contains the
following parameters; (default setting):
- [S1.1] group locking
(- - - unlocked, 1 - locked S1, 2 - locked S1 and P1); (1)
- [S1.2] measured temperature round up
(0.1 °C, 0.2 °C, 0.5 °C, 1.0 °C); (0.5 °C)
SETTING MANUAL
for approximately 5
(
) or
(
) to
for approximately 5
(
) or
(
)
15