3 Descripción del producto
OverC
SPS
MotDrv
SPS
UInd1
SPS
UInd2
SPS
UInd3
SPS
UInd4
SPS
FuncMon
SPS
ParErr
SPS
Settings
BndCtr
ASG
BndWid
ASG
CtlDlTmms
ING
LDCR
ASG
LDCX
ASG
BlkLV
ASG
LimLodA
ASG
© Maschinenfabrik Reinhausen 2013
Current overload
Motor drive running
User indication 1
User indication 2
User indication 3
User indication 4
Function monitoring
Parameter error
Band center voltage (ac-
tual reference)
Band width voltage (as
percent of nominal vol-
tage, FPF presumed)
Control intentional time
delay (FPF presumed, in
seconds)
Line drop voltage due to
line resistance component
(voltage)
Line drop voltage due to
line reactance component
(voltage)
Control voltage below
which auto Lower com-
mands blocked (relative)
Limit Load Current (LTC
Block Load Current, per-
centage)
1801003/05 ES
E
E
E
E
E
E
E
E
O
Unit: V
Multiplier: none
O
Unit: none
Multiplier: c
O
O
Unit: V
Multiplier: none
O
Unit: V
Multiplier: none
O
Unit: none
Multiplier: c
O
Unit: none
Multiplier: c
TAPCON® 260
25