Installation
5
Optional Water Recirculation Setup
Recirculating the water in the system provides constant regulation of the water temperature. Flush the supply
lines thoroughly after completing installation. Close off all fixtures and label them as not available for use
durin g the recirculating process.
Cold
Water
Water
Heater
1. Turn off the recirculating pump and turn on the water supply at emergency fixture (a water flow rate of 10-15 GPM is
required).
2. Let the water run through the system until a consistent temperature is obtained. If you do not obtain the required
temperature, refer to step #3 on previous page for temperature readjustment.
3. As soon as the water reaches the proper temperature, turn on the recirculating pump (make certain the proper system
temperature has been achieved before proceeding).
4. Check the water temperature at the return pump. If the temperature exceeds the appropriate level by 2°F, adjust the
temperature high-limit switch (this will turn off the pump). Wait until the return water temperature is 5°F below the
appropriate level and adjust the low-limit switch (this will turn the pump back on).
5. Open the balancing valve completely.
6. Turn off all fixtures and make sure there is no water running through the system (the cold inlet pipe should feel warm to the
touch).
7. Let the system run for 30 minutes or longer without water. If, after thirty minutes, the water temperature increases, you may
readjust the temperature by slowly closing the balancing valve until the appropriate temperature is reached.
Bradley • 215-1809 Rev. E: ECO 20-09-011
Check Valve (Typ)
Cold
Heat
Trap 28"
Drop
Alternate
Recirculation
(More than 5 GPM)
HOT
Storage
Tank
Check Valve
Return
Balancing
Flow
Valve (Typ)
EFX 20/S19-2150
Tempered Water Flow
Recirculated
Tempered Water
Recirculating
Pump
8/7/2020
Temperature
Switch
7