Configuration (Rvt Specific) - ABB RVT Serie Instrucciones De Instalación Y De Funcionamiento

Ocultar thumbs Ver también para RVT Serie:
Tabla de contenido

Publicidad

2
Protection Temp Sensor
3
Protection U Max
4
Protection T Max
5
Protection External T Max
6
Protection I Max
7
Protection THDU
8
Protection External
9
Protection U Min
5.5.3

Configuration (RVT Specific)

5.5.3.1 Bank Settings (GroupID = 0x0801)
Byte
Description
Offset
0
V nominal
4
V scale
8
1Ph/3Ph/3Ph-
N
9
Lin / Circ
10
Prog/direct
11
Normal /
Integral
12
NOT USED
13
delay ON
17
delay OFF
21
Delay reset
The '1Ph/3Ph/3Ph-N' parameter is defined as follows:
48 Data table ç RVT communication
Data
Units RVT RVT3P
type
V
*
*
Float
*
*
Float
*
*
Byte
*
*
Byte
*
*
Byte
*
*
Byte
*
*
Byte
Sec
*
*
Dword
Sec
*
*
Dword
Sec
*
*
Dword
Value
Description
0
1Ph-1LL1
1
3Ph-1LL1
2
3Ph-1LN1
3
3Ph-3LL3
4
3Ph-3LL2
5
3Ph-3LN3
6
3Ph-1LL3
7
3Ph-1LN3
Temperature sensor lost while monitoring
Overvoltage detection
Internal temperature threshold reached
Temperature sensor threshold reached
Over current detection
THDU threshold reached
External input protection activated
Under voltage detection
Size in
Default
bytes
value
4
400
4
1.0
1
1
1
1
1
1
1
1
1
0
4
40
4
40
4
3
Min
Max
Modb
value
value
@
10
9e6
42801
0.1
10000
42803
0
7
42805
0
1
42806
0
1
42807
0
1
42808
42809
1
64800
42810
1
64800
42812
1
64800
42814

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rvt6Rvt12