Installation Instructions; General Information; Technical Specifications - Johnson Controls York RS1 Instrucciones De Instalación

Sonda remota interior
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 1

Installation Instructions

General information

The RS1 indoor remote probe is designed
to provide close control of the ambient tem-
perature at a location away from that of the
DPC-1 and DPC-1R thermostats.

Technical specifications

This accessory includes the following com-
ponents:
- 15kOhm NTC probe.
- Connecting strip.
- Front cover.
- Probe base.
- Wedges and screws.
Location
To guarantee adequate operation, it should
be installed on an indoor wall, in a frequently
occupies area of the building. Moreover, it
should be at a distance of at least 50 cm.
from any outdoor wall, and at approximately
1.5 m. above floor level, in an are with free air
circulation at an average temperature. The
following locations should be avoided:
- Behind doors or in corners not having free
air circulation.
- Places where direct sunlight or heat com-
ing from other apparatus can alter probe
readout.
- On an outdoor wall.
- Near the discharge grid of an air condi-
General dimensions mm.
tioning unit, stairwells or doors leading
outside.
- Places where operation can be affected by
gas or water pipes, or hot air chimneys or
stacks in adjacent spaces, or in any zone
without environmental control behind the
probe.
- Places where operation is affected by the
supply air of any nearby unit.
- Near sources of electric interferences.
Fastening the remote probe
To fasten the remote probe to the wall, open
the front cover and expose the base of the
probe.
Fasten the probe to the wall with the wedges
and screws supplied.
Take into account that the rectangular hole
located in the inner zone of the base is to
house the electric connection cables.
Installation
It is recommended that installation be car-
ried out by a qualified specialist.
1. Established national regulations must
be followed in all cases.
2. Disconnect power supply to the unit.
3. Use 2 x 0.5 mm
2
screened cable, with a
maximum length of 100 m., between the
thermostat and the probe. Make sure the
��
��
GB
cable is not laid out near power supply
cables.
4. Connections to be made are RS1 and
RS2 on the thermostat side and on the
probe side connecting strip.
5. Connect power supply to the air condi-
tioning unit.
6. Program the origin of the probe as S2.
Caution:
Loose cables can cause over-
heating of the terminals or
incorrect operation of the unit.
Fire hazards may also exist.
Therefore, make sure all cables
are connected tightly.
����������
��
��������������
�����������������������
������������
�����������������������
������
���
������
�����
����������
���������������
��
���������������
���
�����
5

Publicidad

Tabla de contenido
loading

Tabla de contenido