Bosch Praesideo 4.3 Manual De Uso página 56

Sistema de megafonía y sistema acústico de emergencia
Tabla de contenido

Publicidad

Praesideo 4.3
Clause / Requirement
8 Fault warning condition
8. 1 Reception and processing of fault signals
8. 1 . 1 The VACIE shall enter the fault warning condition
when signals are received which, after any necessary
processing, are interpreted as a fault.
8. 1 .2 The VACIE shall be capable of simultaneously
recognizing all of the faults specified in 8.2 and, if provided,
in 8.3 unless this is prevented by:
the presence of an alarm output signal on the same
voice alarm zone, and/or
the disablement of the corresponding voice alarm zone
or function.
8. 1 .3 The VACIE shall enter the fault warning condition
within 100 s of the occurrence of any fault, or the reception
of a fault signal or within another time as specified in this
European Standard or in other parts of EN 54.
8.2 Indication of faults in specified functions
8.2. 1 The presence of faults in specified functions shall be
indicated on the VACIE without prior manual intervention.
The fault warning condition is established when the
following are present:
a
a visible indication by means of a separate light emitting
indicator (the general fault warning indicator);
b
a visible indication for each recognised fault as
specified in 8.2.3, 8.2.4, 8.3 (if provided), 8.4 (if
provided) and 8.5 and
c
an audible indication, as specified in 8.6.
8.2.2 If the indication is on an alphanumeric display, which
cannot simultaneously indicate all of the faults because of
its limited capacity, at least the following shall apply:
a
the presence of fault indications which have been
suppressed shall be indicated;
b
suppressed fault indications shall be capable of being
displayed by means of a manual operation at access
level 1 or 2 which interrogates only fault indications.
8.2.3 The following faults shall be indicated by means of
separate light emitting indicators and/or an alphanumeric
display:
a
an indication at least common to any power supply fault
resulting from:
1
a short circuit or an interruption in a transmission
path to a power supply (item L of Figure 1 of
EN 54-1), where the power supply is contained in a
different cabinet from that of the VACIE, and
Bosch Security Systems B.V.
Compliance
Praesideo is compliant.
When the Praesideo system receives a supervision fault
signal (i.e. detects a fault in the system), the fault warning
condition is entered until this state is explicitly reset.
All Praesideo system faults are handled (acknowledged
and reset) individually. Also, the Praesideo system is
capable of recognizing all of its system faults
simultaneously. The Praesideo system is able to recognize
faults in a voice alarm zone even when there is an alarm
output signal on the zone.
Optional disablement of voice alarm zones or functions is
not implemented in Praesideo.
The Praesideo system recognizes and reports all faults
within 100 seconds.
Praesideo is compliant.
The Praesideo system provides a visible indication when it
is in the fault warning condition via the fault LED of the call
stations, output contacts, key indicators of call station keys,
the fixed fault output contact of the network controller and
the front panel menu of the network controller.
The installer must mount a yellow (flash) light to indicate the
fault warning condition, clearly visible from the front side of
the rack, behind the glass door of the rack.
The Praesideo system offers two ways of visual indication
of individual faults: via the front panel menu of the network
controller and via the Praesideo logging application.
The Praesideo PRS-NCO3 has an internal buzzer for this
purpose. Also, the Praesideo system provides an audible
fault indication when it is in the fault warning condition via
output contacts and the fixed audible fault output contact
of the network controller.
The network controller alphanumeric display is used to
indicate the fault warning condition and all individual faults.
The normal display information of the network controller is
automatically overruled when there are faults present, i.e.
when the system enters the fault warning state. The display
of the network controller indicates the number of faults
present.
The individual faults are presented in the 'Faults' menu of
the front panel menu of the network controller. Manual
operation is needed to display and navigate through the
individual faults. Each individual fault is shown in a
submenu of the 'Faults' menu.
Faults of the supervised items are detected and reported
through the general fault warning indication. Additionally all
faults are reported individually as well and can be inspected
using the network controller front panel menu and the
logging application.
The mains and backup power of all Praesideo system
elements are supervised individually.
Manual de uso e instalación
Signature
IUI-PRAESIDEO_4.3 | V1.0 | 2015.02
es | 56

Publicidad

Tabla de contenido
loading

Tabla de contenido