Installation
1.
Find a suitable location for the RF Contact
Closure Input Interface. Place the interface in a
convenient and accessible location. Note: RF CCI
Interfaces must be located within 30 feet (9 m) of
an RF Signal Repeater or an RF Processor.
2.
Connect external input closures. The RF CCI
Interface will accept up to six low-voltage dry con-
tact closures (see Wiring Diagram). Each terminal
will accept up to three 22-18 AWG (0.5-1.0 mm
wires.
3.
Apply power to the RF Contact Closure Input
Interface.

Wiring Diagram

HR-CCI-6-SW
(Rear View)
Closure
1
Closure
2
Closure
3
2
)
2
Plug in power
cord and
adapter
Closure
6
Closure
5
Closure
4

Mounting Diagram

RF CCI Interfaces may be wall mounted using the
supplied wall bracket.
1.
Attach wall bracket to wall using the supplied
screws and wall anchors.
UP
2.
Place adapter cord into notches at top and bottom
of wall bracket. Place contact closure wiring into
cutout at top of wall bracket. Align interface and
snap onto wall bracket.
Contact Closure
Wiring
UP
Programming Test
The buttons on the front of the RF CCI Interface may
be used to test system programming. Pressing any
button on the interface will override the current state of
the input:
• If the current state is closed, a button press
will cause a Contact Open event. The
release of this button will cause a Contact
Closed event.
• If the current state is open, a button press
will cause a Contact Closed event. The
release of this button will cause a Contact
Open event.