INSTALLATION
Deck-mounted models (Fig. A) :
Drill a hole from Ø 36mm (min.) to Ø 37mm (max.) then tighten the 2 screws onto the fixing flange a.
Ensure a suitable waterproof seal between the mixer and the work surface appropriate to the type
of installation.
Do not remove the non-return valves b incorporated in the water supply pipes (supplied).
Install the filters supplied c (filters and flow rate limiters for ref. H9716), as shown in the diagram.
These will protect the installation. Do not install additional filters.
Balance the hot and cold water pressure (ΔP<1 bar). Recommended pressure 3 bar.
Maximum pressure: 10 bar. Take care not to pinch the flexibles* (Fig. B).
Mounting the spout (Fig. C) :
H9716/H9726: Remove the protective cap and insert the spout in its slot. Remember to include
the flow rate limiter  and waterproof seal  (for washbasin models).
REMEMBER
Our mixers must be installed by professional installers in accordance with current regulations
and recommendations in your country, and the specifications of the fluid engineer.
Sizing the pipes correctly will avoid problems of flow rate, pressure loss and water hammer
(see calculation table in our brochure and online at www.delabie.com).
Protect the installation with filters, water hammer absorbers and pressure reducers to reduce
the frequency of maintenance (recommended pressure from 1 to 5 bar maximum).
Install stopcocks close to the mixer to facilitate maintenance.
The pipework, filters, non-return valves, stopcocks, bib taps, cartridge and all sanitary fittings should
be checked at least once a year, and more frequently if necessary..
GENERAL FEATURES & TECHNICAL INFORMATION
General Features:
In the event of a sudden loss of the cold water supply, and the mixed water temperature selected
is less than 42°C, the hot water supply will be cut-off (within 2 seconds). Filters and non-return valves
at the mixer inlets protect the thermostat and prevent any back-flow into the system.
Technical Information:
The factory pre-set is 38°C, with a temperature range of 50°C between the cold and hot water.
Temperature range for water up to 41°C. First temperature limiter set to 38°C (can be overridden).
It is possible to have water: at 41°C by pressing the button on the control knob  (Fig. E).
Maximum hot water temperature: 90°C.
Min./max. pressure: 1 to 5 bar (recommended 3 bar). Difference in pressure at inlets: max. 1bar.
Safety: the hot water supply will shut off if the cold water supply fails. The hot water failsafe is active
if the hot and mixed water differential is greater than 15°C.
Temperature adjustment control is on the left and the flow-rate control is on the right.
Washbasin flow rate: regulated at 5 lpm. Sink flow rate: regulated at 9 lpm.
TEMPERATURE CALIBRATION (Fig. D)
Our mixers are pre-set at the factory under 3 bar pressure, with balanced hot and cold water supply,
and hot water supply 65°C +/- 5°C and cold water supply at 15°C +/-5°C.
If the conditions of use are different, the mixed water temperature may differ from the temperature shown
on the control lever (38°C). To adjust to the correct temperature:
Open the water supply and measure the temperature using a digital thermometer .
Unscrew the screw  part way using a 2.5mm Allen key and remove the control knob.
Turn the valve spindle  to the right to increase the temperature and to the left to lower it
(15° of rotation for 1°C of temperature).