4. Rotate each lever in the direction indicated until lever is in final latch position. Follow
the latching sequence below to obtain optimum terminal fit.
Use the table below as a guide to insure an adequate gasket seal between terminal and
panel.
1
2
3
4
5
6
Terminal Markings
for Alignment
ATTENTION
!
6
Notch
Alignment Marks
Rotate until notch in levers align
with proper alignment mark on
terminal.
Lever Position
Panel Thickness Range
1
0.15 - 2.01 mm (0.060 - 0.079 in)
2
2.03 - 2.64 mm (0.08 - 0.104 in)
3
2.67 - 3.15 mm (0.105 - 0.124 in)
4
3.17 - 3.66 mm (0.125 - 0.144 in)
5
3.68 - 4.16 mm (0.145 - 0.164 in)
6
4.19 - 4.75 mm (0.165 - 0.187 in)
Follow instructions above to provide a proper seal and
to prevent potential damage to the terminal.
Allen-Bradley assumes no responsibility for water or
chemical damage to the terminal or other equipment
within the enclosure because of improper installation.
Cutout Adapter Kit
1
1
4
Publication 2711P-IN021A-MU-P
7
5
3
6 Levers
2
6
Typical Gauge
16
14
12
10
8/9
7