PROGRAMMING FLOWCHART
*
*
Default values marked with
Entering Menu is always done with B (3 sec) + 000000 if the Master Code is not changed.
Submenu 1 - Change Master Code. The Master Code must be 6 digits. After enrolling new Master Code the MTPAD-M automatically exits the Menu and the new master code must be typed to enter the menu.
Submenu 2 - Select Type of Wiegand. With this the Keypad can be adjusted to send 7 different Wiegand Outputs. The Wiegand selected must be the same as the controller's Wiegand Input where the MTPAD-M
Keypad is being connected. Example: If you use a controller that recognizes Wiegand 34bit, then enter the menu of MTPAD-M, press 2, then press 3.
Submenu 3 - Select Output Protocol. The Keypad can send the Code by different Protocols. Use Codix when connected to Vi200, EX5, EX7, INOX99 or VKP99.
Submenu 4 - PIN Code Length. If "0" is selected, then any PIN Code with any length can be sent, but the PIN Code is typed with "A" for confirmation( ex. 123 + A). If 1 to 8 is selected the PIN Code length is
determinated by the number selected.
Submenu 6 - Presets. The Presets are set of preprogrammed parameters for easy programming.
6-1 "Wiegand 26bit Normal"
- Type: Wiegand 26bit; Output: Single Wiegand; PIN Length: 4 digits; Entry Mode: Card or PIN Code
6-2 "Wiegand 34bit Normal"
- Type: Wiegand 34bit; Output: Single Wiegand; PIN Length: 4 digits; Entry Mode: Card or PIN Code
6-5 "Codix"
- Output: Codix; PIN Length: any length with "A" in the end; Entry Mode: Card or PIN Code
Presets 6-3 and 6-4 to be used always when MTPAD-M is connected to EWS firmware ver.2.42 or higher.
Submenu 7 - Site Code Length. Set the code length sent to Host. Defaul is "0". To be used only in specific cases.
Submenu 8 - Enter Site Code. Put the site code always in 5 digit format (ex. 00170).
Submenu 9 - Backlight. Turns ON/OFF the backlight, buzzer, parity bit.
*
*
*
*
*
*