Modified Sine Wave
Caution
Do not reverse the polarity. Reversing the polarity of the connections will
cause a great spark and the internal fuses will melt.
Caution
Only extend the connection line with cables with and equal or greater cross
section.
Below cross section is for 100% copper wire, does not include thickness of
wire cover.
Device
INV300N
INV600N
INV1000N
INV1500N
INV2000N
6
Switch on at the device
☞
Set the main switch(fig. 1.4 page 2 ) to "ON".
√
The green LED (fig. 1.5 page 2) lights up.
Switch off at the device
☞
Set the main switch(fig. 1.4 page 2 ) to "OFF".
√
The green LED (fig. 1.5 page 2) goes out.
Required cable cross section
100% copper wire
3.00mm²
5.30mm²
10.00mm²
16.00mm²
2x12.00mm²
Using the inverter
10
Connecting the inverter
Cable standard in AWG
(American wire gauge)
14#AWG
10#AWG
8 # AW G
5 # AW G
2x7#AWG