Electrical connection

Protection of the mains connection for the AC•THOR 9s may not exceed 16A per phase (tripping
characteristic B or C).
The PE conductor and the neutral conductor must be connected!
Pay attention to other loads on the line circuit, this may trip the circuit breaker!
The conductor cross-sections at the mains connection and at the load connections must be at
least 2.5 mm².

Operation on one or two phases

The device is also suitable for operation on one or two phases.
Phase L1 must be connected (power supply).
In order to guarantee a perfect control function, outputs whose corresponding phase is not
supplied on the input side must not be connected!
L1 IN → Out1
L2 IN → Out2
L3 IN → Out3

Maintenance

Do not attempt to open the unit. The device does not contain any parts that may be
repaired by the user.
Never splash water on or in the unit!
When power supply is off, the surface of the unit can be cleaned either with a damp cloth, using
mild glass cleaner or cleaning tissue for glasses.
In a polluted environment, the air inlets and outlets should be checked regularly for cleanliness.
If necessary, the unit can be cleaned through the air slots with a vacuum cleaner.
The unit cannot work at maximum efficiency if the air supply is inadequate!
If the mains cable of the unit is damaged, it has to be replaced by the manufacturer or its
service agents or a similarly qualified person.

Operation displays

The unit has a touch screen to show operating conditions and for ease of operation.
Never touch the screen with pointed objects or those having sharp edges!