REMEHA Celcia 20 Guía De Funciones página 11

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

8
EXTRA SETTINGS FOR CELCIA 20 AS WEATHER COMPENSATOR
8.1 Frost protection pump
When the outside temperature is lower than the frost
protection setting, Celcia 20 activates the pump so the
radiators in frost sensitive rooms (e.g. a garage) have
water circulation in order to decrease freezing risk.
Factory setting -10°C. In this case the pump starts at -
10°C and stops again at -9.5°C.
To change the value:
Set the rotary knob on MENU
§
Go to the SETTINGS option and press OK
§
Go to the CONTROLLER option and press OK
§
Go to PUMP FROST and press OK
§
Set the required value and select OK
§
Return the rotary knob to the desired programme
§
and close the lid.
8.2 Deactivate pump at daytime
This function only works when Celcia 20 works as a
weather compensator. The intention is to decrease the
run hours of the pump. It works as follows: If the outside
temperature is higher than the pre-set room temperature
(TEMP-1 to TEMP-5) + this value, Celcia 20 deactivates
the boiler pump.
Example: setting 1°C, room temperature setpoint 20°C.
The boiler is switched off at 20+1+0.5 = 21.5°C and on
at 20+1-0.5 = 20.5°C. Factory setting 1°C.
To change the value:
Set the rotary knob on MENU
§
Go to the SETTINGS option and press OK
§
Go to the CONTROLLER option and press OK
§
Go to CONTROL and press OK
§
Select WEATH COMPENS and press OK
§
Go with the OK-button to PUMP OFF DAY
§
Set the required value and select OK
§
Return the rotary knob to the desired programme
§
and close the lid.
8.3 Deactivate pump at night
This function only works when Celcia 20 works as a
weather compensator. The goal is to decrease the run
hours of the pump. It works as follows: If the outside
temperature is higher than the pre-set room temperature
(ECO-TEMP) + this value, Celcia 20 deactivates the
boiler pump.
Example: setting -5°C, room temperature setpoint 15°C.
The boiler is switched off at 15-5+0.5 = 10.5°C and on
at 15-5-0.5 = 9.5°C. Factory setting -5°C.
To change the value:
Set the rotary knob on MENU
§
Go to the SETTINGS option and press OK
§
Go to the CONTROLLER option and press OK
§
Go to CONTROL and press OK
§
Select WEATH COMPENS and press OK
§
Go with the OK-button to PUMP OFF NGHT
§
Set the required value and select OK
§
Return the rotary knob to the desired programme
§
and close the lid.
8.4 Booster function for weather-compensated
heating
A booster function allows for accelerated heating up,
following in increase of the set temperature. Should this
lead to problems (skyrocketing temperature levels), the
booster function may be shut off. The booster function is
activated at delivery.
Set the rotary knob on MENU
§
Go to the SETTINGS option and press OK
§
Go to the CONTROLLER option and press OK
§
Go to BOOSTER and press OK
§
Select YES or NON and select OK
§
Return the rotary knob to the desired programme
§
and close the lid.