Descargar Imprimir esta página

Publicidad

Enlaces rápidos

Betriebsanleitung
Brandmelder IQ8Quad mit Alarmgeber
Operating Instruction
Fire Detector IQ8Quad with alarm device
(Art.-Nr. / Part No. 80238x)
Technische Änderungen vorbehalten!
GB
I
798931
Technical changes reserved!
D
01.2009
© 2009 Honeywell International Inc.
E
F
Novar GmbH a Honeywell Company
Dieselstraße 2, D-41469 Neuss
Internet:
www.esser-systems.de
E-Mail:
info@esser-systems.de
Abb. 1: Brandmelder und Meldersockel (Art.-Nr. 805590)
Fig. 1: Fire detector and detector Base (Part No. 805590)
Spezifische Melderdaten / Detector Specifications
Alarmgebertyp / Alarm device type
Ruhestrom @ 19 V DC / Quiescent current @ 19 V DC
Ruhestrom @ BMZ
/ Quiescent current @ FACP
Akku
Lastfaktor / Load factor
Max. Schallpegel @ DIN-Ton / Max. Sound level @ DIN tone
Lichtstärke / Strenght of light
Blitzenergie Blitzleuchte, rot / Flashing energy flashing light, red
Warntongeberspezifikation / Audible alarm device specification
CE-Zertifikat / CE certificate
Achtung
Brandmelder dienen dem Schutz von Personen und
Sachwerten und sollten nach der Installation auf die
einwandfreie Funktionalität überprüft werden.
Bei einer fehlerhaften Installation ist die ordnungsgemäße
Funktion nicht gewährleistet!
Bitte nationale Normen und Richtlinien beachten!
Brandmelder nur mit Rauchmeldertestgerät 805581 /
805582 / 769870.20 und Prüfgas 060430.10 / 769070
testen!
Anwendung
Automatischer, busfähiger optischer bzw. thermooptischer
Brandmelder mit integriertem Alarmgeber und Leitungstrenner
zum Anschluss an die esserbus
Brandmeldesystems IQ8Control. Die Alarmierung erfolgt im
Ereignisfall, abhängig von dem Alarmgebertyp, wahlweise per
Blitzleuchte, Warnton und/oder Sprachmeldung.
Systemvoraussetzungen
Brandmelderzentrale IQ8Control mit Betriebssystemsoftware
ab V3.02
®
esserbus
-PLus Funktionalität
Programmiersoftware tools 8000 ab Version 1.07
Falschalarmquellen für Rauchmelder
Aerosole
mit
sichtbaren
Verbrennungsmaschinen, Zigarettenrauch, Wasserdampf oder
Staubablagerungen.
Berechnung der maximalen Signalgeberanzahl
Die zulässige Anzahl von busfähigen Alarmgebern auf der
Analog-Ringleitung ist abhängig vom Alarmgebertyp und der
Ringleitungslänge. Hierzu sind die individuellen Lastfaktoren
der einzelnen Busteilnehmer zu addieren (siehe Spezifische
Melderdaten). Der max. zulässige Gesamtlastfaktor einer
einzelnen Ringleitung beträgt 96.
Montage / Meldersockel (Abb. 1)
Die Brandmelder werden direkt in den zugehörigen Standard
Meldersockel (Art.-Nr. 805590) eingesetzt. Schutzart IP 43 mit
Zubehör Art.-Nr. 805570, 805572, 805573.
Inbetriebnahme / Wartung
Die Inbetriebnahme und Wartung von Brandmeldern ist nur
durch
qualifiziertes
Brandmeldesystem eingewiesenes Fachpersonal zulässig.
Der Brandmelder und der integrierte Alarmgeber wird in der
Kundendatenprogrammierung
IQ8Control konfiguriert. Alle Funktionen und der Zustand des
Brandmelders werden zyklisch melderintern geprüft und
während
des
Prüfbetriebs
übertragen
und
dort
unzulässigen Arbeiten an dem Brandmelder erlöschen die
Garantie- und Gewährleistungsansprüche.
Ergänzende und aktuelle Informationen
Die Produktangaben entsprechen dem Stand der
Drucklegung und können durch Produktänderungen,
geänderte Normen/Richtlinien ggf. von den hier
genannten Informationen abweichen.
Aktualisierte Informationen, Konformitätserklärungen
und Instandhaltungsvorgaben siehe www.esser-
systems.de.
®
esserbus
und essernet
eingetragenes Warenzeichen.
Allgemeine Technische Daten
Betriebsspannung
Überwachungsfläche
Überwachungshöhe
Luftgeschwindigkeit
Anwendungstemperatur
Lagertemperatur
Luftfeuchte
Schutzart
Material
Farbe
Gewicht
Maße (mit Sockel)
Melderspezifikation
VdS-Anerkennung
Für Brandmelder mit akustischem Alarmgeber ist
werkseitig der DIN-Signalton voreingestellt.
Zur Ermittlung der Akkukapazität einer BMZ
können die Werte Ruhestrom @ BMZ
werden!
Zur Konfiguration der Melder 802385.SVxx und
802386.SVxx, Hinweise in der Programmier-
software tools 8000 beachten!
2
802383
O
T/F-
Multisensormelder /
Multisensor Detector
Optisch /
visual
75 µA
400 µA
Accu
2
---
max. 15,8 cd peak;
2,63 cd effective
~ 3 J
---
0786-CPD-20193
D
®
-PLus Ringleitung des
Partikeln,
wie
z.B.
durch
und
im
Umgang
mit
dem
des
Brandmeldesystems
des
Systems
zur
Zentrale
im
Störungsfall
angezeigt.
Bei
®
sind in Deutschland ein
: 8 V DC bis 42 V DC
: max. 110 m²
: max. 12 m
: 0 bis 25,4 m/s
: -20 °C bis +65 °C
: -25 °C bis +75 °C
: ≤ 95 % rel. Feuchte
(ohne Betauung)
: IP 43 (mit Sockel + Zubehör)
: ABS
: weiß (ähnlich RAL 9010)
: ca. 145 g
: Ø 117 mm, H = 65 mm
: EN 54-7/-5 B/-17, CEA 4021
: G 205111
addiert
Akku
2
802384
O
T/So-
802385 / 802385.SVxx
Multisensormelder /
Multisensormelder /
Multisensor Detector
Multisensor Detector
Akustisch /
optisch, akustisch + Sprache /
audible
visual, audible + speech
80 µA
450 µA
2
92 dB (A) ± 2 dB
max. 15,8 cd peak;
---
---
GB
Safety Notice
Fire detectors provide fire hazard protection for people and
property. After installing the detector it is thus crucial to check
carefully to ensure that the units are working properly.
Proper functioning cannot be guaranteed if the detectors are
not installed correctly in accordance with the instructions!
Please observe the relevant national regulations and
guidelines!
Use only smoke detector tester 805581 / 805582 /
769870.20 and test gas 060430.10 / 769070 to test smoke
detector operation!
Application
Intelligent photoelectric / heat fire detector with integrated
alarm device and loop isolator for operation on the Powered
®
Loop (esserbus
-PLus) of the Fire Alarm System IQ8Control.
The alarm signal depends on the corresponding alarm device
type, respectively as an flashing light, audible signal and/or
speech message.
System requirements
Fire Alarm Control Panel IQ8Control with operating system
software from V3.02
Powered loop operation mode features
Programming software tools 8000 from Version 1.07
False alarm sources for photoelectric smoke detectors
Visible airborne particles or vapor, e.g. combustion engine
exhausts, cigarette smoke, steam or dust deposits.
Calculating the total number of alarm devices
The number of loop alarm devices is limited by the type of the
alarm device and the loop length. Therefore the individual load
factors must be added (refer to General Specifications). The
total load factor for a single loop must not exceed 96.
Mounting / Detector base (Fig.1)
These detectors are mounted directly on the matching
Standard detector base (Part No. 805590). Protection rating
IP 43 with options Part No. 805570, 805572, 805573.
Commissioning / Maintenance
The commissioning and maintenance of the Fire Alarm
Detectors must be carried out only by an experienced
technician who is familiar with the Fire Alarm System
IQ8Control.
All detector functions and device status are checked at regular
intervals by the integrated diagnostics. The results are
transferred to the control panel and any errors are displayed
there when the System is in test mode. Any unauthorized work
on or tampering with the detector will void all warranty and
guarantee claims.
Additional and updated Informations
The product specification relate to the date of issue
and may differ due to modifications and/or amended
Standards
and
Regulations
informations.
For updated informations, declaration of conformity
and maintenance specifications refer to www.esser-
systems.de.
®
®
esserbus
and essernet
are registered trademarks
in Germany.
General Specifications
Operating voltage
: 8 V DC to 42 V DC
Mounting area
: max. 110 m²
Mounting height
: max. 12 m
Air velocity range
: 0 to 5.000 ft/min.
Application temperature
: -20 °C to +65 °C
Temperature, storage
: -25 °C to +75 °C
: ≤ 95% relative,
Ambient humidity
(non-condensing)
Protection rating
: IP 43 (with base + options)
Housing
: ABS
Colour
: white (similar to RAL 9010)
Weight
: approx. 145 g
Dimensions (with base)
: Ø 117 mm, H = 65 mm
Detector specifications
: EN 54-7/-5 B/-17, CEA 4021
VdS Approval
: G 205111
Fire alarm detectors with audible alarm device are
configured by factory with a DIN tone preset.
To determine the battery capacity of a FACP
battery, the values of the quiescent current @
FACP
can be added!
Accu
Please refer to the tools 8000 programming
software for information on the configuration of
sensor 802385.SVxx and 802386.SVxx.
2
O
T/FSp-
802386 / 802386.SVxx
Multisensormelder /
Multisensor Detector
akustisch + Sprache /
audible + speech
90 µA
500 µA
3
92 dB (A) ± 2 dB
92 dB (A) ± 2 dB
2,63 cd effective
~ 3 J
EN 54-3
0786-CPD-20192
from
the
given
2
O
T/Sp-
90 µA
500 µA
3
---
---

Publicidad

loading

Resumen de contenidos para Honeywell 80238 Serie

  • Página 1 Powered loop operation mode features Technical changes reserved! • • 01.2009 Programmiersoftware tools 8000 ab Version 1.07 Programming software tools 8000 from Version 1.07 © 2009 Honeywell International Inc. Falschalarmquellen für Rauchmelder False alarm sources for photoelectric smoke detectors Aerosole sichtbaren Partikeln, z.B.
  • Página 2 Avvertenze Atención Attention • • • I rilevatori d'incendio servono per proteggere le persone e le cose Los detectores de incendios sirven de protección para las Les détecteurs d’incendie servent à protéger les personnes dagli incendi. Pertanto, in seguito all'installazione del sensore è personas y elementos de valor y, una vez instalados, se debe et les biens et leur fonctionnement parfait devrait être vérifié...

Este manual también es adecuado para:

Esser iq8quad