Betriebsanleitung
Brandmelder IQ8Quad mit Alarmgeber
Operating Instruction
Fire Detector IQ8Quad with alarm device
(Art.-Nr. / Part No. 80238x)
Technische Änderungen vorbehalten!
GB
I
798931.10
Technical changes reserved!
D
04.2018 / AB
© 2018 Honeywell International Inc.
E
F
Novar GmbH a Honeywell Company
Dieselstraße 2, 41469 Neuss, Germany
Tel.: +49 2131 40615-600
Fax: +49 2131 40615-606
www.esser-systems.com
info@esser-systems.com
Abb. 1: Brandmelder und Meldersockel (Art.-Nr. 805590)
Fig. 1: Fire detector and detector Base (Part No. 805590)
Spezifische Melderdaten /
Detector Specifications
Alarmgebertyp / Alarm device type
Ruhestrom @ 19 V DC / Quiescent current @ 19 V DC
Ruhestrom @ BMZ
/ Quiescent current @ FACP
Akku
Lastfaktor / Load factor
Blitzenergie Blitzleuchte, rot /
Flashing energy flashing light, red
Lichtstärke / Strenght of light
Spezifikation Warntongeber /
Specification Audible alarm device
Spezifikation / specifications
VdS-Anerkennung / VdS Approval
Leistungserklärung / Declaration of Performance
Achtung
Brandmelder dienen dem Schutz von Personen und Sachwerten
und sollten nach der Installation auf die einwandfreie
Funktionalität überprüft werden.
Bei einer fehlerhaften Installation ist die ordnungsgemäße
Funktion nicht gewährleistet!
Bitte nationale Vorschriften / Richtlinien beachten!
Anwendung
Automatischer, busfähiger optischer bzw. thermooptischer Brandmelder
mit integriertem Alarmgeber und Leitungstrenner zum Anschluss an
®
den esserbus
-PLus der ESSER-Brandmelderzentralen. Die Alarmierung
erfolgt im Ereignisfall, abhängig von dem Alarmgebertyp, wahlweise
per Blitzleuchte, Warnton und / oder Sprachmeldung.
Systemvoraussetzungen
BMZ Compact, BMZ IQ8Control, BMZ FlexES Control
(mit aktuellen Software Versionen)
BMZ mit esserbus
Service- und Programmiersoftware tools 8000
Falschalarmquellen für Rauchmelder
Aerosole mit sichtbaren Partikeln, wie z.B. durch Verbrennungs-
maschinen, Zigarettenrauch, Wasserdampf oder Staubablagerungen.
Falschalarmquellen für Thermomelder
Schneller, heftiger Anstieg der Umgebungstemperatur, Klima-/
Umluftanlagen.
Berechnung der maximalen Signalgeberanzahl
Die max. Anzahl von busfähigen Signalgebern auf dem esserbus
PLus ist abhängig vom Signalgebertyp und der Ringleitungslänge.
Hierzu die individuellen Lastfaktoren der einzelnen Busteilnehmer
addieren (siehe spezifische Melderdaten). Der max. zulässige
Gesamtlastfaktor einer Ringleitung beträgt 96.
Montage / Meldersockel (Abb. 1)
Die Brandmelder werden direkt in den zugehörigen Standard Melder-
sockel (Art.-Nr. 805590) eingesetzt.
Inbetriebnahme
Die Inbetriebnahme und Wartung von Brandmeldern ist nur durch
qualifiziertes
und
eingewiesenes Fachpersonal zulässig. Bei unzulässigen Arbeiten an
dem Brandmelder erlöschen die Garantie- und Gewährleistungsan-
sprüche.
Wartung
Alle Funktionen und der Zustand des Brandmelders werden zyklisch
melderintern geprüft und eine erforderliche Wartung automatisch
angefordert. Während des Prüfbetriebs des Systems werden die Daten zur
Zentrale übertragen und dort im Störungsfall angezeigt (Anzeige der
entsprechenden Störungscodes auf dem Zentralendisplay beachten).
Brandmelder ausschließlich mit der Service- und
Programmiersoftware tools 8000 in Betrieb nehmen,
prüfen bzw. warten!
Rauchmelder nur mit Rauchmeldertestgerät
(Art.-Nr. 805551 / 805582) und Prüfgas
(Art.-Nr. 805552 / 805584) testen!
Thermomelder nur mit Thermomeldertestgerät
(Art.-Nr. 805551 / 060429) testen!
Ergänzende und aktuelle Informationen
Die Produktangaben entsprechen dem Stand der
Drucklegung und können durch Produktänderungen,
geänderte Normen / Richtlinien ggf. von den hier
genannten Informationen abweichen.
Aktualisierte Informationen, Konformitätserklärungen und
Instandhaltungsvorgaben siehe www.esser-systems.com.
®
esserbus
eingetragene Warenzeichen.
Allgemeine Technische Daten
Betriebsspannung
- Melder
- Trenner
- Alarmgeber
Überwachungsfläche
Überwachungshöhe
Luftgeschwindigkeit
Anwendungstemperatur
Lagertemperatur
Luftfeuchte
Schutzart
Material
Farbe
Gewicht
Maße (mit Sockel)
Für Brandmelder mit akustischem Alarmgeber ist
werkseitig der DIN-Signalton voreingestellt.
Weitere Angaben siehe Technische Information 798960.
Die Ermittlung der erforderlichen BMZ-Notstromkapazität
erfolgt über die Programmiersoftware tools 8000 bzw. über
die Berechnung unter www.esser-systems.com.
Zur Konfiguration der Melder 802385.SVxx und
802386.SVxx, Hinweise in der Programmier-software
tools 8000 beachten!
802382 O/So-
Multisensormelder /
Multisensor Detector
Multisensor Detector
Akustisch /
audible
50 µA
320 µA
Accu
2
---
---
EN 54-3:2006
EN 54-7:2006 /-17:2005
G 206090
DoP-20242130701
D
®
-PLus Funktionalität
im
Umgang
mit
dem
Brandmeldesystem
®
und essernet
sind in Deutschland
: 8 V DC ... 42 V DC
: 14 V DC ... 42 V DC
: 27 V DC ... 42 V DC
: max. 110 m²
: max. 12 m
: 0 ... 25,4 m/s
: -20 °C ... +65 °C
: -25 °C ... +75 °C
: 95 % rel. Feuchte (ohne Betauung)
: IP 40 ... 43 (mit Sockel + Option)
: ABS
: weiß (ähnlich RAL 9010)
: ca. 145 g
: Ø 117 mm, H = 67 mm
802383 O
2
802384 O
2
T/F-
T/So-
Multisensormelder /
Multisensormelder /
Multisensor Detector
Optisch /
Akustisch /
visual
audible
75 µA
80 µA
400 µA
450 µA
2
2
~ 3 J
---
max. 15,8 cd peak;
---
2,63 cd effective
---
EN 54-3:2006
DoP-20193130701
Safety Notice
Fire detectors provide fire hazard protection for people and
property. After installing the detector it is thus crucial to check
carefully to ensure that the units are working properly.
Proper functioning cannot be guaranteed if the detectors are not
installed correctly in accordance with the instructions!
Please observe the relevant national regulations and guidelines!
Application
Intelligent photoelectric / heat fire detector with integrated alarm
device and loop isolator for operation on the esserbus
ESSER Fire Alarm Control Panels. The alarm signal depends on the
corresponding alarm device type, respectively as a flashing light,
audible signal and/or speech message.
System requirements
FACP Compact, FACP IQ8Control, FACP FlexES Control
(with current software versions)
®
FACP with esserbus
PLus functionality
Service and programming software tools 8000
False alarm sources for photoelectric Smoke detectors
Visible airborne particles or vapor, e.g. combustion engine exhausts,
cigarette smoke, steam or dust deposits.
False alarms for Heat detectors
Rapid, substantial increases in ambient temperature, air conditioning
and ventilation systems.
Calculating the total number of alarm devices
®
The max. number of esserbus
®
PLus alarm devices is limited by the
-
type of the alarm device and the loop length. Therefore the individual
load factors must be added (refer to detector specifications). The
total load factor for a loop must not exceed 96.
Mounting / Detector base (Fig.1)
These detectors are mounted directly on the matching Standard
detector base (Part No. 805590).
Commissioning
The commissioning and maintenance of the Fire Alarm Detectors
must be carried out only by an experienced technician who is familiar
with the Fire Alarm System. Any unauthorized work on or tampering
with the detector will void all warranty and guarantee claims.
Maintenance
All detector functions and device status are checked at regular
intervals by the integrated diagnostics and provide an automatic
maintenance. The results are transferred to the control panel and any
errors are displayed there when the System is in test mode (Observe
corresponding fault codes in the panels display).
Commission, test and maintain fire detectors only with the
service and programming software tools 8000!
Use only smoke detector tester (Part No. 805551 /
805582) and test gas (Part No. 805552 / 805584) to test
smoke detector operation!
Use only test head for heat detector
(Part No. 805551 / 060429) to test heat detector operation!
Additional and updated Informations
The product specification relate to the date of issue and
may differ due to modifications and/or amended Standards
and Regulations from the given informations.
For updated informations, declaration of conformity and
maintenance specifications refer to www.esser-systems.com.
esserbus
®
and essernet
Germany.
General Specifications
Operating voltage
- Detector
- Isolator
- Alarm device
Mounting area
Mounting height
Air velocity range
Application temperature
Temperature, storage
Ambient humidity
Protection rating
Housing
Colour
Weight
Dimensions (with base)
Fire alarm detectors with audible alarm device are
configured by factory with a DIN tone preset.
For more information see Technical Information 798960.GB0.
The FACP emergency power capacity is determined using
the programming software tools 8000 or via the calculation
function available at www.esser-systems.com.
Please refer to the tools 8000 programming software
for information on the configuration of sensor
802385.SVxx and 802386.SVxx.
802385 / 802385.SVxx O
2
T/FSp-
Multisensormelder /
Multisensor Detector
optisch, akustisch + Sprache /
visual, audible + speech
90 µA
500 µA
3
~ 3 J
max. 15,8 cd peak;
2,63 cd effective
EN 54-3:2006 + Sprach / speech
EN 54-7:2006/-5 B:2000/-17:2005, CEA 4021
G 205111
DoP-20192130701
GB
®
PLus of the
®
are registered trademarks in
: 8 V DC ... 42 V DC
: 14 V DC ... 42 V DC
: 27 V DC ... 42 V DC
: max. 110 m²
: max. 12 m
: 0 ... 5.000 ft/min.
: -20 °C ... +65 °C
: -25 °C ... +75 °C
: 95% relative, (non-condensing)
: IP 40 ... 43 (with base + option)
: ABS
: white (similar to RAL 9010)
: approx. 145 g
: Ø 117 mm, H = 67 mm
802386 / 802386.SVxx
2
O
T/Sp-Multisensormelder /
Multisensor Detector
akustisch + Sprache /
audible + speech
90 µA
500 µA
3
---
---