14 Insulation for the refrigerant pipe

a. The refrigerant pipe should be insulated by the insulating material and plastic
tape in order to prevent condensing and leaking.
b. The joints of the indoor unit should be wrapped with the insulating material and
no gas is allowed on the joint of the indoor unit, as shown in Fig.19.
CUATION!
After the pipe is protected well enough, never bend it to form a small angle;
otherwise it would crack or break.
c. Wrapping the pipe with tape.
1) Bundle the refrigerant pipe and electric wire together with tape, and separate
them from the drain pipe to prevent the condensate water overflowing.
2) Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where
it enters the wall. During the wrapping, the later circle should cover half of the former
one.
3) Fix the wrapped pipe on the wall with clamps.
CUATION!
①. Do not wrap the pipe too tightly; otherwise the insulation effect would be
weakened. Additionally, make sure the drain hose is separated from the pipe
②. After that, fill the hole on the wall with sealing material to prevent wind and rain
coming into the room.

15 Wiring between the Wire and the Wiring Terminal

a. Wiring of the Single-Core Wire
Unitary Duct Split Unitary Duct Split
Fig.19
16