Technical Specifications - Bosch FCP-O 500 Manual De Instalación

Ocultar thumbs Ver también para FCP-O 500:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 9
Automatic Fire Detector
1
Installation
Notes
Inserting color rings (P-Variants)
See Graphics, page 4.
1.
2.
3.
4.
Mounting the detector and trim ring
See Graphics, page 4.
Notice!
Use of the FAA‑500‑RTL exchanger device is recommended for removing and inserting the
detectors.
1.
2.
3.
Dismantling the detector and trim ring
1.
2.
2

Technical Specifications

Operating voltage
Current consumption
Indicator output
Minimum installation
height
Bosch Sicherheitssysteme GmbH
Carefully cut open the packaging of the detectors with C sensor.
Do not remove the protective film from the detector head until installation is finished.
The detector front plate (1) is secured with a small snap-fit hook (2) on the three‑way
guideway. To remove, insert the enclosed opening tool (3) in the slot (4) above the snap-
fit hook, secure it with your thumb, turn the front plate counterclockwise and lift.
From the selected color, place the color rings (5) on the front plate (1) and put on the
detector. Only one position of the front plate is possible.
Turn the cover clockwise to lock it into place. Ensure the sensor windows lie free.
Insert the selected color ring in the trim ring (6).
Snap the trim ring into place on the base (7).
Remove the protective film from the detector head.
On startup, a protective film left on the detector by mistake is recognized by the system.
A fault message will occur.
Press the detector one time gently upwards into the base. The push/push system holds
the detector.
Due to the guideways, the detector can only be placed in the base in the correct position.
For high mounting heights: The clearly visible two contact plates (8) in the base are on
the same side as the single guideway (9).
Press the detector one time gently upwards into the base. The push/push system
releases the detector.
Lift the trim ring by the edge to remove it from the base.
8.5 to 30 V DC
Standby
FCA-500-EU: 3 mA
FCA-500-E-EU: 24 mA
Alarm
47 mA
Fault
FCA-500-EU: 52 mA
FCA-500-E-EU: 58 mA
Relay connects 0 V over 1.5 kΩ
Out of arm's reach
Minimum installation height recommended by BOSCH: 2.70 m
Installation manual
Installation | en
7
2019.11 | 5.0 | F.01U.002.684