According to UL 60947-4-1 Use wire Cu 75°C only. Use built-in cable clamps or UL recognized compression lugs. Enclosure with min. dimension 24 by 20 by 10
inches should be used. Suitable for use on a circuit capable of delivering not more than the max. symmetrical amperes at the max. voltage shown in the table below.
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 208-240V (kA)
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 208-240V (kA)
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
ABB AB, Control Products
SE -721 32 Västerås, Sweden
Telephone +46 21 32 07 00
Telefax +46 21 12 60 01
http://www.abb.com/lowvoltage
T4*, XT4*
250/RK5
250/J
5
100
10
10
Definite Purpose magnetic motor controller. Breaking all lines. Max 600V AC, 50/60 Hz:
Herm. ref. comp, AC-8a
TYPE
FLA
116
AF(S)116
AF140
125
160
AF(S)146
T4N250
T4S250
65
100
100
25
35
100
18
25
XT4N250 XT4S250 XT4H250 XT4L250 XT4V250 XT4X250
65
100
25
35
18
22
Ballast, AC-5a/
Resistance air heating
LRA
800
160
875
200
200
1050
T4H250
T4L250
T4V250 XT4X150
100
100
100
65
100
100
35
65
100
100
100
100
65
100
100
25
50
65
Elevator duty
54
54
54
4/4
100
100
100
100
100
65