Interconnection
Direct Connection
2-Wire Extension
Coaxial Extension
Note:
Grounding transducer as shown is mandatory per safety regulations and for
isolation against electrical interference.
Installation
Installation shall only be performed by qualified personnel and in accordance with local
governing regulations.
Do not route cable openly; instead run cable separately in a grounded metal conduit to
protect it from ambient electrical noise.
Seal all thread connections to prevent the ingress of moisture.
Do not run cable near high voltage or current runs, contactors or SCR control drives.
For pressure tight applications, install transducers hand tight plus ½ turn to 1½ turns.
PTFE tape or other appropriate sealant may be used to aid in sealing the threads for use
in pressure applications.
WARNING:
Improper installation may result in loss of process pressure.
7ML19985QS81
XLT Series Transducers – OPERATION MANUAL
Siemens Milltronics controller (typical)
blk
blk/hot
wht/shld
wht
junction
box
blk
drain/shield
wht
extend cable using 18 AWG shielded/twisted pair
extend cable using RG - 62 A/U coax for optimum
signal to noise ratio
Page EN-7