Descargar Imprimir esta página

Publicidad

Enlaces rápidos

PINSLVPC-20-PT (REV. C)
ENGLISH
IN U.S.A.: Cooper Wiring Devices, 203 Cooper Circle, Peachtree City, GA 30269 • 866-853-4293
PLUGS AND CONNECTORS (16/20A-30/32A)
NOTICE: READ ALL INSTRUCTIONS COMPLETELY BEFORE INSTALLING THIS DEVICE
This pin and sleeve device conforms to International Electrotechnical Commission Standards IEC 60309-1 and 60309-2.
DO NOT USE non-IEC devices in the same application as IEC devices, unless assured that no improper mating can occur.
GENERAL INFORMATION:
• NOTICE: For installation by a qualified electrician in accordance with national and local electrical codes and the
following instructions.
• CAUTION: RISK OF ELECTRICAL SHOCK. Disconnect power before installing. Never wire energized electrical components.
• CAUTION: USE COPPER CONDUCTORS ONLY.
1. Check that the device's type and rating are suitable for the application.
2. Use stranded conductors ONLY. Acceptable sizes are shown in Table 1.
3. The pilot contact (if installed) is rated A600 pilot duty, 600VAC 10A.
Suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical amperes, 600V
maximum when protected by Non-time delay types CC, J, or T class fuses.
INSTALLATION
1. Select cord end with proper conductor color that matches terminal location.
2. Shear cord cleanly. Do not strip away cord jacket or remove conductor insulation at this time.
3. Disassemble device. Refer to Figure 1.
a. Loosen two cord clamp screws (9) and cord clamps (8).
b. Loosen cord grip assembly (7) from housing (4).
c. Loosen two assembly screws (2) from face of device and remove terminal assembly (1) from device housing (4).
4. Wiring Instructions
a. Slide cord grip assembly (7) up cord.
b. Slide washer (6) up cord if possible. Do not use washer if it does not fit on cord.
c. NOTE: the cord diameter range is marked on the grommet. Select a grommet (5) suitable for cord outside diameter and slide
the grommet up the cord.
d. Slide device housing (4) up cord.
e. Strip cable jacket and conductor insulation as described in Table 3. DO NOT TIN CONDUCTORS.
f. Twist wire strands together on each conductor.
g. Select ferrule suitable for wire size (small for #14AWG, medium for #12AWG, large for #10AWG). No ferrule is needed when
using #8AWG wire in the 30/32 amp devices.
h. Loosen terminal screws (3). Insert conductors into ferrule and fully insert ferrule with conductors into proper terminals as
identified in Table 2.
i. Tighten terminal screws to torque shown in Table 3.
j. TAKE CAUTION THAT THERE ARE NO STRAY WIRE STRANDS.
5. Reassemble device
a. Assemble terminal housing by tightening two screws (2) until terminal assembly (1) is firmly seated in housing (4) .
b. Slide grommet (5), washer (6), and cord grip assembly (7) down cord to housing and fully tighten the cord grip to hard stop to
compress grommet.
c. Tighten the set screw (10) on the cord grip assembly to prevent the cord grip from turning.
d. Assemble cord clamps (8) and tighten cord clamp screws (9) to 12 in-lbs (1.3 N-m).
FIGURE 1. EXPLODED VIEW / FIGURE 1. VUE ÉCLATÉE / FIGURA 1. VISTA EN DESPIECE
1. Terminal assembly / Ensemble de bornes / Conjunto del terminal
2. Assembly screws / Vis d'assemblage / Tornillos de ensamblaje
3. Terminal screws / Vis de bornes / Tornillos de los terminales
4. Housing / Boîtier / Carcasa
5. Grommet / Passe-fil / Anillo protector
6. Washer / Rondelle / Arandela
7. Cord grip assembly / Ensemble de serre-câble / Conjunto de agarre del cordón
8. Cord clamp / Étrier de serre-câble / Abrazadera del cordón
9. Cord clamp screws / Vis de serre-câble / Tornillos de la abrazadera del cordón
10. Set screw / Vis de pression / Tornillo de fijación
3
1
2
TABLE 1
NUMBER OF
DEVICE
CONDUCTORS
3 or 4
16-20A
5
GROUND
3 or 4
5
30-32A
GROUND
PILOT
ALL
TABLE 2
TERMINAL POLARITY IDENTIFICATION TABLE
TERMINAL
G, GREEN, OR
N or W
L1, L2, L3
Pilot
TABLE 3
DEVICE
Strip cable jacket length
Strip conductor length
Torque terminal screws
(including pilot
terminal) to
10
7
6
5
4
ACCEPTABLE CONDUCTOR WIRE SIZES
FROM
TO
CORD GRIP RANGE
MIN/MAX. DIA
AWG
TYPE
AWG
TYPE
#12
S
#10
S
#12
S
#10
S
#12
#10
#10
S
#8
S or W
#10
S
#8
S or W
#10
#8
#16
#12
CONDUCTOR
Equipment grounding conductor (Green, Green
Yellow, Bare)
Ground Circuit Conductor Neutral (White or Gray)
Unground Circuit Conductor (Line, Hot)
Control circuit conductor
20A
16 A
Inch
2
mm
51
Inch
0.33
mm
8.3
In-Lbs
10
N-m
1.1
9
8
10
0.333/0.775
0.433/0.840
0.433/0.985
0.433/1.150
30A
32 A
2.75
70
0.60
15.2
10
1.1
9

Publicidad

loading

Resumen de contenidos para Cooper Wiring Devices 16/20A

  • Página 1 PINSLVPC-20-PT (REV. C) ENGLISH IN U.S.A.: Cooper Wiring Devices, 203 Cooper Circle, Peachtree City, GA 30269 • 866-853-4293 PLUGS AND CONNECTORS (16/20A-30/32A) NOTICE: READ ALL INSTRUCTIONS COMPLETELY BEFORE INSTALLING THIS DEVICE This pin and sleeve device conforms to International Electrotechnical Commission Standards IEC 60309-1 and 60309-2.
  • Página 2 FRANÇAIS IN CANADA: Cooper Wiring Devices, 5925 McLaughlin Road, Mississauga, Ontario L5R 1B8 • 800-267-1042 FICHES MâLES ET FEMELLES (16/20A-30/32A) AVIS : VEUILLEZ LIRE TOUTES LES INSTRUCTIONS AU COMPLET AVANT D’INSTALLER CET APPAREIL TABLEAU 1 Cet appareil à broches et manchons est conforme aux normes de la Commission Électrotechnique CALIBRES AWG ACCEPTABLES POUR LES CONDUCTEURS Internationale IEC 60309-1 et 60309-2.

Este manual también es adecuado para:

30/32a