Descargar Imprimir esta página

Lutron PD8-PNL-8-SUB Instrucciones De Instalación página 2

Retroadaptación de subplacas din

Publicidad

Idiomas disponibles

Idiomas disponibles

7. Install QS link harness
Using the provided cable ties, secure the QS link harness to the right side of
the subplate. See image below.
NOTE: Dress low-voltage (Class 2) wires away from line-voltage wires per
local and national codes.
Cable Ties
8. Mount the DIN Power Modules (DPMs)
Mount the DIN Power Modules (DPMs) onto the DIN rail rows aligning them to
the right. Mount with arrow pointing up to ensure adequate cooling. Mount to
DIN rail by pressing module onto rail with clips pressed in. To remove from rail,
pull clips out using a screwdriver. Also remove QS link connector from each
unit. See DPM install guide for more details. If panel had a Ten Volt Module kit,
see Step 12 for 0-10 V wiring. NOTE: If installing LQSE-4A5-120-D modules,
first add wiring to panel terminal blocks, then mount the module and move to
Step 9.
0,26 in
0,28 in
50016659a
6,5 mm
7 mm
Prog.
Zn. 1
Zn. 2 Zn. 3 Zn. 4
Ta > 65 ˚C
1
HomeWorks QS
2
LQSE-4S8-120-D
120 V~ 8 A
120 V~ 50 / 60 Hz 16 A
3
L
M
lutron.com
+1.844.LUTRON1
120 V~ 8 AX, 1/3 HP
L
N
N N N N
1
2
3
4
0,26 in
Cu
Al
65 / 75 °C
4,4 in-lb
6,5 mm
0,5 N
m
Ensamblado en México
Assembled in Mexico
Inc. Cont. Eq. 243C
Assemblés aux Mexique
Lutron Electronics Co., Inc.
7200 Suter Road, Coopersburg, PA 18036-1299
9. Wire the DIN Power Modules (DPMs)
Install mains, load, and QS link wiring to each of the DPMs. LQSE-4T5-120-D
shown for reference. See DPM install guide for more details. If panel had a Ten
Volt Module kit, see Step 12 for 0-10 V wiring.
5 /16 in
4.4 in-lb
8 mm
0.5 N•m
HomeWorks QS
Input | Entrada
Entrée
Def
LQSE-4T5-120-D
Ta > 65 ˚C
1
120 V~ 50 / 60 Hz
Prog
2
lutron.com
+1.844.LUTRON1
120 V~ 5 A ea
3
H
N
1
2
N
N
N
N
N
DH1
DH2
DH3
DH4
H
10. Install panel cover
Install panel cover using the new cover provided. Use the existing RPM panel
screws (8-32 x 3/8 in) that were set aside in Step 2a. If the RPM panel being
upgraded is a control panel, go to Step 11 now
NOTE: The existing remote power panel cover CANNOT be reused, and will
H
void the warranty if used.
Customer Assistance: www.lutron.com/support U.S.A., Canada, and the Caribbean: 1.844.LUTRON1 | Mexico: +1.888.235.2910 | Other: +1.610.282.3800
11. If upgrading a RPM control panel
If upgrading a RPM control panel then install the cover plate (included) on the
back of the cover. Use the (x4) provided black screws (8-32 x 3/8 in).
Zn 1
Zn 2
Zn 3
Zn 4
H
Opt
M
L
3
4
12. 0-10 V panel only
Wire the 0–10 V wires to a LQSE-4T5-120-D module. Ensure 0-10 V wiring
is kept separate from line voltage wiring by running wires down right side of
panel. Lutron recommends a terminal block kit "PDT-T-1", which gets mounted
in module position 8. PDT-T-1 must be purchased separately to make the
connection between the existing 0-10 V wires and the new 0-10 V module.
Can fit a maximum of six PDT-T-1 kits on DIN rail position 8.
Zn 1
Zn 2
Zn 3
Zn 4
5 /16 in
4.4 in-lb
8 mm
0.5 N•m
Input | Entrada
HomeWorks QS
Entrée
LQSE-4T5-120-D
Def
H
Ta > 65 ˚C
Ta > 65 ˚C
1
Opt
120 V~ 50 / 60 Hz
1
Opt
Prog
2
M
lutron.com
+1.844.LUTRON1
2
3
L
120 V~ 5 A ea
3
L
H
N
1
2
3
4
13. Install bypass jumpers
Install bypass jumpers if any load or fixture wiring has been modified.
14. Install cover, turn on power and check for errors
Install cover, turn on power and check for errors. If any circuit breakers trip,
an error needs to be resolved.
15. Remove cover and remove bypass jumpers
Remove cover and remove bypass jumpers once wiring has been verified.
16. Install cover and restore power to the panel
Install cover and restore power to the panel and each branch circuit. If lights
do not turn on, an error needs to be resolved. Verify wiring and loading on
each module. See DPM install guides for troubleshooting steps for each
module.
17. Program the new DPMs
Using the HomeWorks programming tool, the link type will need to be changed
from a panel link to a QS link to establish communication with the new DPMs.
Must also setup each DPM output for the correct load type.
DIN Power Modules (DPM) Supported
Model Number
LQSE-4A5-120-D
Screws (x4)
LQSE-4S8-120-D
LQSE-4T5-120-D
LQSE-4M-120-D
RPM to DPM Replacement Recommendations
RPM Model Number
HW-RPM-4A-120 / HW-RPM-4E-120
HW-RPM-4R
RPM with GRX-TVM2
HW-RPM-4M-120
HW-RPM-4U-120
HW-RPM-4FSQ-120
Low-
voltage
Barrier
PDT-T-1
Terminal
Block Kit
0–10 V
Wiring
0–10 V DPM
Retrofit
Subplate
Need Help? wwww.lutron.com/support or call Lutron Customer Assistance Center,
at 1.844.LUTRON1
Limited Warranty: For warranty information, please see the warranty enclosed with the product,
or visit: www.lutron.com/TechnicalDocumentLibrary/Warranty
Lutron, HomeWorks, and LED+ are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the
US and/or other countries. All other product names, logos, and brands are property of their respective owners.
©2021 Lutron Electronics Co., Inc.
Description
PRO LED+ Phase Adaptive Module
Switching Module
0-10 V / Switching Module
Motor Module
DPM Model Number
LQSE-4A5-120-D
LQSE-4S8-120-D
LQSE-4T5-120-D
LQSE-4M-120-D
Phase: LQSE-4A5-120-D
Switching: LQSE-4S8-120-D
0-10 V: LQSE-4T5-120-D
Mixed: LQSE-4A5-120-D with PHPM or
TVI interfaces
HQRD-2ANF or change to 0-10 V fans

Publicidad

loading