Installation Instruction
Features
The EE900M is used to evacuate condensate liquid, parti-
cularly in noise sensitive environments such as hotel and
bedrooms. Low noise levels are achieved due to the slow
movement of the piston.
The pump maintains its flow rate, almost irrespective of
the discharge height.
The EE900M has 2 control options i. e. temperature sen-
sor and a 3-level float sensor.
Technical Specifications EE900
•
Pump (LxBxH):
•
Electrical spec.:
•
Alarm switch:
•
Max. flow rate:
•
Max. suction:
•
Max. discharge:
•
Flexible piping:
•
IP-rating:
•
Weight:
Electrical connections:
Brown:
Blue:
Green / yellow:
Red:
White:
M
ca. 152 x 85 x 114mm
230V, 50Hz, 10VA
48V AC/DC / 1,5A
(resitive load,NO normally
open, (Only in combination
with a floater)
ca. 6 l/h
ca. 2m (4m at request)
ca. 7m
6 x 2mm
20
ca. 700g
Phase
Neutral
PE
Alarm contact
Alarm contact
Installation Note
The suction and discharge connections use
flexible piping of Ø 6mm ID.
After installation activate the test switch, which will run the
pump for about 3 minutes.
Please always install the pump vertically, never in a
lying position. (see picture)
Control via temperature sensor
Install the pump in the ceiling space using the provided
mounting holes. Connect the temperature sensor to the
pump. The installation has to be touch-safe. Not to be
installed in damp or humid environments.
The red sensor measures the ambient temperature ("air
on"). The blue sensor measures the temperature of the
cold air-conditioner airflow ("air off"). The pump starts
working at a temperature difference of 7°C.
WARNING: Sensors must never touch the gills of the
heat exchanger!
- 4 -