18
INSTALLATION INSTRUCTIONS
venting the Dryer (cont.)
ductwork
NUMBER OF
WALL CAP TYPE
90° ELBOWS
Recommended
4"
(10.2 cm)
4"
(10.2 cm)
Use only for
short run
installations
2
/
"
2
4
(6.35 cm)
NOTE
Deduct 6 ft. (1.8 m) for each additional elbow. It is not
recommended to use more than four 90° elbows.
routing and connecting ductwork
NOTE
Follow the guidelines below to maximize drying
performance and reduce lint buildup and
condensation in the ductwork.
Ductwork and fittings are NOT included and must be
purchased separately.
• Use 4-inch (10.2 cm) diameter rigid or semirigid
metal ductwork.
• The exhaust duct run should be as short as possible.
• Use as few elbow joints as possible.
• The male end of each section of exhaust duct must
point away from the dryer.
• Use duct tape on all duct joints.
• Insulate ductwork that runs through unheated areas
in order to reduce condensation and lint buildup on
duct surfaces.
• Incorrect or inadequate exhaust systems are not
covered by the dryer warranty. Failures or poor
performance caused by such exhaust systems will
not be covered by the dryer warranty.
MAxIMUM LENGTH
OF 4-INCH (10,2 CM)
DIAMETER RIGID
METAL DUCT
0
65 ft. (19.8 m)
1
55 ft. (16.8 m)
2
47 ft. (14.3 m)
3
36 ft. (11.0 m)
4
28 ft. (8.5 m)
0
55 ft. (16.8 m)
1
47 ft. (14.3 m )
2
41 ft. (12.5 m)
3
30 ft. (9.1 m)
4
22 ft. (6.7 m)
CORRECT VENTING
INCORRECT VENTING