Setting and using method
4. Control mode setting
n Use the CONTROL_MODE_SW to set the control mode you
want from 0~E.
CONTROL_MODE_SW
Ú Indoor control priority
Central control > Dry Contact For Setback > Wired/Wireless remote controller, indoor unit button
Ú Dry Contact For Setback controls the indoor unit according to the applicable mode when there is a
change in input of A and B.
n Description of each control mode
1) Cancel mode for use of Dry contact for setback
CONTROL_
MODE S/W
0
Ú Set this when the Dry Contact For Setback is connected but not used.
12 Dry Contact for setback
Input A
Input B
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Operating mode
The indoor unit cannot be controlled through the
Dry contact for setback
No change in indoor unit condition