Note
The operating modes of the "A2S" and "BR" are not certified.
ED300
Optical-heat detector with heat sensitive element and optical smoke chamber. The combination of
values provides (in accordance with the operating mode selected via the control panel) high immunity to
nuisance alarms and an exceptionally sensitive detector which is capable of swift response to fires cha-
racterized by low smoke emission.
Operating mode
Mode
The operating modes, programmable via the control panel are:
"PLUS" (pre-set); the detector signals alarm status when smoke in the protected environment
exceeds the programmed threshold (programmed as described for the ED100 model) or when the
temperature within the protected environment exceeds the programmed threshold (programmed as
described for the ED200 model). Furthermore, in the event of a rise in temperature within the pro-
tected environment, the sensitivity of the smoke chamber will be increased. This operating mode, cha-
racterized by high sensitivity, allows detection of fires which produce a large amount of flames but
low smoke emission (e.g. combustion of alcohol or similar highly-inflammable products).
"OR"; the detector signals alarm status when smoke in the protected environment exceeds the pro-
grammed threshold (programmed as described for the ED100 model) or when the temperature
within the protected environment exceeds the programmed threshold (programmed as described for
the ED200 model). This operating mode, characterized by medium-high sensitivity, allows detection
of fires which generate a substantial amount of smoke but low heat emission (slow burning fires) as
well as fires which generate high temperatures and low smoke emission (chemical products).
"AND"; the detector signals alarm status when the smoke and temperature in the protected envi-
ronment exceed the programmed thresholds simultaneously (programmed as described for
theED100 model and ED200 model respectively). This operating mode, characterized by a low sen-
sitivity, lowers the false alarm rate and is useful in applications where either the smoke or heat
values in the protected environment may increase without the risk of fire.
Note
Given the limited response, consider the conditions in the protected environment carefully
before selecting this operating mode.
"SMOKE"; the detector assumes the characteristics of the ED100 model
"HEAT"; the detector assumes the characteristics of the ED200 model
LED
The three-colour LED (360° viewing) indicates the detector status.
Green blinking at 15-second intervals; the detector is in standby status (i.e. operating properly).
Green On solid; the LED has been activated manually from the control panel. This operation allows
easy identification of the detector.
Yellow On solid; the detector is in fault status or has detected a short-circuit in the succeeding wiring
section (short-circuit isolator open). Further details regarding the fault can be obtained through the
control panel.
Red On solid; the detector is in alarm status. Further details regarding the alarm can be obtained
through the control pane
"R" terminal
The detectors have an output (terminal "R"), for the connection of an alarm repeater LED. This LED will
activate in accordance with programming carried out via control panel.
The detector is also capable of discerning whether its repeater LED has been connected. This function
provides indications (on the control panel) regarding the detectors with connected LEDs, and also fault
signals in the event of disconnection.
Description of the parts
A Detector
B Detector notch
C Thermal probe
D Red/yellow/green LED
E Optical chamber
F Technical specifications/serial-number sticker
G Removable serial-number stickers
H Cover removing hooks
I Optical chambre removing hooks
Installation
Note
For information regarding device placement, coverage and method of installation, refer to the
established standard regulations and codes relating to Automatic fire-detection systems.
Enea series detectors are compliant with EN54-7: Smoke detectors – Point detectors using the
scattered light principle, light transmission or ionization (ED100 and ED300 models only) and
EN54-5: Heat detectors – point detectors (forED200 and ED300 models only), EN54-17 short-
circuit isolators.
Manuale d'istruzioni/ Instruction manual/ Manualde instrucciones/ Notice d'instructions
The detectors are supplied with protective covers which help to protect them against minor damage and
dust contamination which may occur during the installation phase. The covers should not be removed
until the system is ready to start up.
The detectors can be used with one of the following compatible mounting bases:
EB0010; standard base
An example of installation using standard bases is shown opposite.
EB0020; relay base
Appropriate when the detector is to be connected to an intrusion control panel or to a control panel
using 4 wires.
Note
The two removable serial-number stickers should be taken off and one should be attached to
the mounting base and the other to the installation layout.
Once the base is located properly in its placement, place the detector unit onto the base and, with mini-
mum force, turn it clockwise until the detector notch [B] aligns with the base notch [K] (in order to attach
the detector to the base); turn it still further until notch [B] aligns with the second base notch [L] (in order
to allow the base to engage with the detector contacts).
When installation of all the loop devices is complete, proceed with the addressing phase. Refer to the
respective section in the control panel installation and programming manual.
Using the EDRV2000 driver
The EDRV2000 driver allows you to change the operating parameters of the detectors, check the con-
tamination level of the smoke chambers and also obtain accurate diagnostic data. It can operate through
the USB port of a computer furnished with the relative software programme, or can function auto-
nomously by way of the battery housed inside.
Each detector is capable of retaining memory (smoke and/or temperature depending on the model) of
the 5 minutes prior to an alarm. Therefore, if an alarm occurs, it will be possible to obtain information
regarding the onset of the fire by simply connecting the EDRV2000 driver to the detection line.
For further information and details regarding use of the EDRV2000 driver, refer to the respective hand-
book.
Testing and maintenance
After installation and during periodic maintenance inspections, you must carry out the following ope-
rations on each detector:
Optical smoke detector test; smoke detectors should be tested immediately after installation and perio-
dically during maintenance inspections in accordance with the established standard regulations and
codes in force. To test smoke detectors, use an approved test aerosol strictly in accordance with the
accompanying instructions.
Ensure that the smoke inlet ports to the smoke detection chamber are not blocked. Check the con-
tamination level of the smoke detection chamber via the control panel. If the contamination level is high
(above 50%), detach the detector from its mounting base, open the device and, using a small, soft-bristle
brush or hand-held vacuum cleaner remove all dust particles from inside and around the smoke detec-
tion chamber.
Free the protection mesh from all contaminants.
Heat detector test; using a suitable device (e.g. hairdryer), create heat in the vicinity of the detector,
then work through the steps described in the device instruction sheet. During each periodic maintenance
inspection, ensure that the heat element is intact and that is not obstructed by dust or paint. If it is, using a
small, soft-bristle brush or hand-held vacuum cleaner remove all contaminants.
Technical specifications
Model
J Base
K Base notch 1
Power supply
L Base notch 2
Current draw in standby
M "+" terminal
N "-" terminal
Current draw in alarm
O "R" terminal
P Short-circuit reed
Current draw by the "R" output
Q Screw locations
(internally limited)
Dimensions (DxH, standard base
included)
Weight
Environmental conditions
Temperature
Relative humidity
ED100
ED200
ED300
from19 to 30 V
200µA
10mA @27,6V
Max 14mA
110 x 46 mm
110 x 54 mm
160g, standard base included
91g, without base
from -5 to +40 °C
≤ 95 % without condensation
Inim ElectronicsS.r.l. © 2020
CE mark
0051
INIM Electronics s.r.l.
Via Dei Lavoratori 10 - Fraz. Centobuchi
Via Dei Lavoratori 10 - Fraz. Centobuchi
63076 Monteprandone (AP) - Italy
63076 Monteprandone (AP) - Italy
10
0051-CPR-1878
EN 54-7:2000 + A1:2002 + A2:2006
EN 54-17:2005
ED100
Intelligent analogue addressable optical smoke detec-
Intelligent analogue addressable class P heat detec-
tor with short circuit isolator for fire detection and fire
tor with short circuit isolator for fire detection and fire
alarm systems installed in buildings
alarm systems installed in buildings
Essential characteristics
Performance
Essential characteristics
Nominal activation con-
Nominal activation con-
dition/sensitivity, response delay
dition/sensitivity, response delay
PASS
(response time) and performance
(response time) and performance
under fire conditions
under fire conditions
Operational reliability
PASS
Operational reliability
Tolerance to supply voltage
PASS
Tolerance to supply voltage
Temperature resistance
PASS
Vibration resistance
PASS
Durability of
Durability of
operational
Humidity resistance
PASS
operational
reliability:
reliability:
Corrosion resistance
PASS
Electrical stability
PASS
Detector class (EN54-5): A1R or B
Documents for the users
Declarationsof Performance, Declarationsof Conformity
and Certificatesconcerning to Inim ElectronicsS.r.l. pro-
0051
ductsmaybe downloaded free of charge from the web
INIM Electronics s.r.l.
addresswww.inim.biz, getting accessto Extended
Via Dei Lavoratori 10 - Fraz. Centobuchi
Accessand then selecting "Certifications"or requested to
63076 Monteprandone (AP) - Italy
the e-mailaddressinfo@inim.bizor requested byordi-
10
narymailto the addressshown in thismanual.
0051-CPR-1876
EN 54-5:2000 + A1:2002
Manualsmaybe downloaded free of charge from the
EN 54-7:2000 + A1:2002 + A2:2006
web addresswww.inim.biz, getting accessto Extended
EN 54-17:2005
Accessand then selecting "Manuals".
ED300
Intelligent analogue addressable multicriteria optical
Warnings and limitations
smoke and class P heat detector with short circuit iso-
Enea series detectors must be used exclusively with
lator for fire detection and fire alarm systems installed
fully compliant, compatible controlpanels. Detectors
in buildings
may not provide timely warning of fire if coverage is
limited by large obstructions (pillars, large machinery,
Essential characteristics
Performance
etc.). When installing or working on a fire detection
system, always refer to and comply with the esta-
Nominal activation con-
blished standard regulations and codes. Appro-
dition/sensitivity, response delay
PASS
priate fire-risk assessment should be undertaken to
(response time) and performance
determine the type of detectors required and their
under fire conditions
placements.
Operational reliability
PASS
Tolerance to supply voltage
PASS
Temperature resistance
PASS
Vibration resistance
PASS
Durability of
operational
Humidity resistance
PASS
reliability:
Corrosion resistance
PASS
Electrical stability
PASS
Detector class (EN54-5): A1R or B
Manufacturer's details
About this manual
Manufacturer: Inim ElectronicsS.r.l.
Manual code: DCMIIN1PED
Production plant: Centobuchi, via DeiLavoratori10
Revision: 250
63076 Monteprandone (AP), Italy
Copyright: the information contained in thisdocument
Tel: +39 0735 705007
isthe sole propertyof Inim ElectronicsS.r.l. No part may
Fax: +39 0735 734912
be copied without written authorization from Inim Elec-
e-mail: info@inim.biz
tronicsS.r.l.. Allrightsreserved.
Web: www.inim.biz
The personsauthorized bythe manufacturer to repair
or replace the partsof thissystem, hold authorization to
workon Inim Electronicsbrand devicesonly.
WEEE
lnformative notice regarding the disposal of electrical and electronic equipment (applicable in
countries with differentiated waste collection systems)
The crossed-out bin symbolon the equipment or on itspackaging indicatesthat the product must be disposed
of correctlyat the end of itsworking life and should never be disposed of together with generalhousehold
waste. The user, therefore, must take the equipment that hasreached the end of itsworking life to the appro-
priate civicamenitiessite designated to the differentiated collection of electricaland electronicwaste. Asan alternative to
DCMIIN1PED-250-20200618
0051
INIM Electronics s.r.l.
10
0051-CPR-1877
EN 54-5:2000 + A1:2002
EN 54-17:2005
ED200
Performance
PASS
PASS
PASS
Temperature resistance
PASS
Vibration resistance
PASS
Humidity resistance
PASS
Corrosion resistance
PASS
Electrical stability
PASS