Electrical Installation - Pahlen Aqua compact Instrucciones De Instalación

Ocultar thumbs Ver también para Aqua compact:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 33
Electric heater Aqua compact

Electrical installation

WARNING
• The electrical installation may only be carried out by a qualified electrician in accordance
with the instructions provided with the heater.
• As electrical installation regulations differ from country to country, contactors, cables,
connection components, and enclosures must be selected based on local regulations.
• A main isolator must be installed before all live electrical connections on the heater. This
must be an all-pole isolator that satisfies the requirements set out in IEC/EN 60335-1
paragraphs 7.12.2, 22.2 and 24.3.
• Pahlén recommends the installation of a residual current device.
• The heater must be connected according to the wiring diagram below.
• The control voltage is connected: for 230 V 1-phase and 400 V 3-phase to L1 and N,
for 230 V 3-phase to L1 and L2.
Note that the control voltage must be fitted with a separate fuse of 5-10 amps for the live
electrical connections.
• The heater must be installed in such a way that it cannot be activated unless the circulation
pump is in operation (sufficient flow), i.e. the control current to the heater's contactors must
be controlled over the pump's contactors.
• The voltage to the heater must not fluctuate more than +5% to –10% in relation to the
specification of the model and type plate.
• The installation method must be chosen in such a way that the temperature limit is not
exceeded for any component at full load.
Minimum requirements for contactors (main isolator) and coupling material
Connection options
Isolator poles
Voltage
Power
Current
Temperature
* See the table "Rated power and power consumption"
** The temperature the component receives at the installation site at the maximum ambient temperature, but at least +45º and
the maximum power output from the heater. The temperature depends on how well ventilated the installation is.
NOTE!
Installed cables are only test cables. These must not be used for connection.
230 V, 1-phase
2
240 VAC
According to the rating
plate*
According to the rating
plate*
60ºC**
12
230 V, 3-phase
4
240 VAC
According to the rating
plate*
According to the rating
plate*
60ºC**
ENGLISH
400 V, 3-phase
4
-415 VAC
According to the rating
plate*
According to the rating
plate*
60ºC**

Publicidad

Tabla de contenido
loading

Tabla de contenido