1.5. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty level.
Range: 0.0000 to 20.000 m
Values
1.6. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level.
Range: 0.0000 to 20.000 m
Values
1.7. Apply? (Apply changes)
In order to save the Quick Start settings it is necessary to select Yes to apply changes.
Options
Display shows DONE when Quick Start is successfully completed.
Press Mode
to return to Measurement mode. SITRANS LR200 is now ready to operate.
Requesting an Echo Profile
1)
In PROGRAM mode, navigate to: Level Meter >
Diagnostics (3) > Echo Profile (3. 1 ).
2)
Press RIGHT arrow
3)
In the Profile screen, press UP arrow
the Transmit icon, and RIGHT arrow
the profile.
4)
Press DOWN arrow
then RIGHT arrow
SITRANS LR200 Communications: HART
• You will need the full manual to acquire the list of applicable parameters.
• We recommend that you use SIMATIC Process Device Manager (PDM) to program your
device.
SIMATIC PDM
Notes:
• SIMATIC PDM Rev. 6.0 SP3 or higher is recommended.
• SIMATIC PDM Rev. 5.2 SP1 is supported only for basic configuration and troubleshooting.
For advanced features such as the Quick Start wizard, Revision 6.0 SP3 or higher is
required.
SIMATIC PDM is a software package used to commission and maintain SITRANS LR200 and
other process devices. Please consult the operating instructions or online help for details on
using SIMATIC PDM. (You can find more information at: www.siemens.com/simatic-pdm. Go to
Products and Solutions > Products and Systems > Communications and Software > Process
Device Manager.)
Page EN-20
SITRANS LR200 (HART) – QUICK START MANUAL
YES, NO
to request a profile.
to select the Exit icon,
to return to previous menu.
DIAGNOSTICS
ECHO PROFILE
MEAS. VALUES
REMAIN. DEV. LIFE
RE
MAIN SENS. LIFE
.
to select
to update
C:38 A:TF D:4.25
1
2
3
transmit icon,
selected
3.1
transmit icon,
deselected
exit icon,
selected
4
5
exit icon,
deselected
7ML19985XC81