Electrical Connections; Instrumentation; Power On Light; Vessel Pressure Gauges - Ingersoll Rand HRD Serie Manuel De Instrucciones

Secadores de aire comprimido
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

fold piping before the dryer is operated. Desiccant
dusting may cause a restriction in the purge exhaust
muffler shortly after start-up. Depending on the dryer
model, the muffler cores may be in the control enclo-
sure or strapped to a vessel leg. For additional infor-
mation see Desiccant Dusting in the Maintenance
section, page 10.
WARNING
Operating dryer without mufflers will cause
noise levels exceeding OSHA standards.
Remove mufflers only for servicing and
maintenance and only after internal pressure
of dryer has been completely vented to
atmosphere.

Electrical Connections

The dryer is prewired, ready for use. Connect the dryer
to the power supply specified on the data plate. Con-
nections, marked L1 and L2, are on a terminal strip in-
side the electrical box. Make connections through the
plugged hole (identified by a tag) on the bottom right
of the box.
DANGER
Ground the dryer using the connection
supplied inside the electrical box. Refer to the
electrical schematic at the back of this manual
for connection details.
Important Note: Do not switch power to the dryer
on and off via a remote disconnect. To avoid dryer
malfunction, power to the unit must be switched on
and off using the switch on the dryer control panel.

INSTRUMENTATION

The following instrumentation helps in monitoring
dryer operation and performance. Instruments which
are available as options are so noted.

Power ON Light

The power ON light on the control panel indicates
when the dryer is turned on and operating.

Vessel Pressure Gauges

A gauge mounted on the gauge bracket indicates
which vessel is onstream and which is regenerating.
The gauge for the onstream vessel indicates operating
pressure; the gauge for the regenerating vessel indi-
cates 0 psig.
1-4

Purge Flow Indicator

A gauge mounted on the gauge bracket of the dryer in-
dicates purge air pressure as an approximate measure
of purge airflow when used with the calibration graph
shipped with the dryer. To approximate purge airflow,
locate the pressure gauge reading (psig) on the hori-
zontal axis of the graph. Follow the pressure upward
until it intersects the calibration curve. Follow this
point to the left until it intersects the vertical axis. This
point on the vertical axis is approximately the purge
airflow.

Switch-Failure Alarm (Optional)

Pressure sensors located on each vessel trigger both
audible and visible alarms if a vessel does not depres-
surize at the completion of its drying cycle. A red
light, labeled SWITCH FAILURE, is located on the
electrical panel. A time-delay relay is included sepa-
rately in the dryer packaging. The relay must be
mounted into the electrical panel before start-up. The
electrical schematic at the back of this manual gives
wiring details.
High-Humidity Alarm (NEMA Type 1, 4 ,
12) (Optional)
A moisture sensor in the dryer outlet manifold moni-
tors the relative humidity of the outlet air. The sensor
triggers audible and visible alarms if the relative hu-
midity of the outlet air exceeds the factory setting. The
audible alarm is located near the control enclosure. A
red light, labeled HIGH HUMIDITY, is located on the
electrical panel. A set-plug adjustment bulb (refer to
Figure 9) is included for use in calibrating the high-
humidity alarm. Contacts for remote annunciators are
connected to the terminal strip in the electrical enclo-
sure; refer to the electrical schematic for terminal
numbers. Refer to the maintenance section of this
manual for field adjustment instructions.

Moisture Indicator (Optional)

A color-change moisture indicator is shipped sepa-
rately in a moisture-proof bag. The moisture indicator
should be installed in a customer-supplied 1¼-inch
NPT threaded port at the dryer outlet. The indicator is
green when dry. The color changes to yellow when the
relative humidity of the dryer outlet air is approxi-
mately 4%-5%. This indicator is intended only as an
inexpensive means of determining possible dryer mal-
function.
Dew Point Monitor (NEMA Type 1, 4, 12)
(Optional)
The monitor is between the vessels beneath the electri-
cal box. It continuously displays outlet pressure dew
HRD Series (Bulletin 348)

Publicidad

Tabla de contenido
loading

Tabla de contenido