System example
TB7 TB3
TB7 TB3
Outdoor unit
Central controller
24 VDC
(G-50 A)
12 VDC
Power supply unit
PAC-SC50KUA
Transmission Booster (No.2) should be used, if the total equivalent trans-
mission power consumption reaches 6.
* When multiple Transmission Booster are used, connect all Transmission Booster to Indoor/Outdoor transmission line system (TB3).
Outdoor
unit
10
01
ME remote
controller
Transmission Booster (No.1) should be used, if the total quantity of Indoor units, OA pro-
cess units and ME remote controllers reaches 40, (Indoor unit sized P200, 250 is counted
as 2); or if the total equivalent transmission power consumption reaches 32.
LOSSNAY
LOSSNAY
unit
unit
PZ-52SF
N3
PAC-
PAC-
SF46EPA
SF46EPA
TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA
WEIGHT
POWER RATING
220-240V:0.7A ~/N
3.4kg
50
MADE IN JAPAN
Transmission
02
Booster
PAC-SF46EPA
(No.1)
N1
UP
MODEL
TRANSMISSION BOOSTER
PAC-SF46EPA
POWER RATING
220-240V:0.7A ~/N
50
WEIGHT
3.4kg
MADE IN JAPAN
Transmission
Booster
LOSSNAY
PAC-SF46EPA
unit
(No.2)
PZ-52SF
N4
Within N4, the total equivalent transmission
power consumption should not exceed 25.
Outdoor
unit
UP
ME remote
controller
N2
Within N2, conditions 1,2 should be followed.
1. The total quantity of Indoor units, OA process units and ME
remote controller should not exceed 40.
*Indoor unit sized P200, 250 is counted as 2 units.
2. The total equivalent transmission power consumption should
not exceed 25.
PAC-
SF46EPA
PAC-
SF46EPA