Functions
1.1.1.44
Loads
-
Incandescent lamps
-
230 V halogen lamps
-
LV halogen lamps via Busch electronic transformers
-
LV halogen lamps via conventional transformers
CAUTION
Conventional transformers and Busch electronic
transformers must not be dimmed together.
All other load combinations are permissible.
Calculation of the Rated Power Output
Use the following formula to calculate the rated power
output:
Rated power output = Transformer losses* + luminaire
wattage
* with electronic transformers, 5% of the rated power
ofthe transformer
* with conventional transformers, 20% of the rated
power of the transformer